Hitachi SJ2002 manual Terminal Tightening Torque and Wire Size, Awg

Models: SJ2002

1 34
Download 34 pages 41.24 Kb
Page 4
Image 4

Terminal Tightening Torque and Wire Size

The wire size range and tightening torque for field wiring terminals are presented in the tables below.

200V Models

Motor output

Inverter Model

 

Wire Size

Torque

 

 

 

 

 

kW

HP

 

 

(AWG)

ft-lbs

(N-m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.2

1/4

–002NFE(F)2/NFU2

 

 

 

 

 

 

 

 

 

 

 

0.4

1/2

–004NFE(F)2/NFU2

 

16

0.6

0.8

 

 

 

 

 

 

 

0.55

3/4

–005NFE(F)2

 

 

 

 

 

 

 

 

 

 

 

0.75

1

–007NFE(F)2/NFU2

 

14

 

 

 

 

 

 

 

 

1.1

1 1/2

–011NFE(F)2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

2

–015NFE(F)2/NFU2

 

12

0.9

1.2

 

 

 

 

 

 

 

2.2

3

–022NFE(F)2/NFU2

 

10

 

 

 

 

 

 

 

 

 

3.7

5

–037LFU2

 

10

 

 

 

 

 

 

 

 

 

5.5

7 1/2

–055LFU2

 

10

1.5

2.0

 

 

 

 

 

7.5

10

–075LFU2

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400V Models

 

 

 

 

 

 

 

 

 

 

Motor output

Inverter Model

 

Wire Size

Torque

 

 

 

 

 

kW

HP

 

 

(AWG)

ft-lbs

(N-m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.4

1/2

–004HFE(F)2/HFU2

 

 

 

 

 

 

 

 

 

 

 

0.75

1

–007HFE(F)2/HFU2

 

16

 

 

 

 

 

 

 

 

1.5

2

–015HFE(F)2/HFU2

 

0.9

1.2

 

 

 

 

 

 

 

2.2

3

–022HFE(F)2/HFU2

 

 

 

 

 

 

 

 

 

 

 

 

 

3.0

4

–030HFE(F)2

 

14

 

 

 

 

 

 

 

 

 

4.0

5

–040HFE(F)2/HFU2

 

 

 

 

 

 

 

 

 

 

 

5.5

7 1/2

–055HFE(F)2/HFU2

 

12

1.5

2.0

 

 

 

 

 

 

 

7.5

10

–075HFE(F)2/HFU2

 

 

 

 

 

 

 

 

 

 

 

2