Error

Name

Probable Cause(s)

Code

 

 

 

 

 

 

 

 

E35

Thermistor

• Thermistor input, [THM] and [L], is

 

 

over the temp. threshold

E60

Communications error

• The inverter’s watchdog timer for the

 

 

communications network has timed out.

---

Under-voltage (brownout)

• Low input voltage caused the inverter

with output shutoff

to turn OFF the motor output and try to

 

 

 

restart. If unsuccessful, a trip occurs.

 

 

 

Error Trip Conditions

Use function code D081 to access the error trip conditions for the current error as shown in the table below. Use the Up and Down arrow keys to scroll through the trip condition parameters.

 

Step

Display

 

 

 

 

 

 

1.

Access D081

d081

 

 

 

 

 

2.

Press Function Key

If no error:

 

 

_ _ _

 

 

 

 

 

If error exists:

 

 

EXX

 

 

(error code)

 

 

 

3.

Press Up/Dn key (if

Output frequency at trip point:

error exists)

10.0

 

 

Motor current at trip point:

12.5

DC bus voltage at trip point:

284.0

2Cumulative Run time house at trip point:

15

Cumulation power-ON hours at trip point:

18

14