Function List

 

 

 

 

 

 

Default

 

 

Run mode

Function Code

 

Name

Range

 

 

 

Unit

 

edit

 

 

 

 

 

-EF(CE)

-U(UL)

-R(JP)

 

 

 

 

 

 

 

 

 

 

Lo

 

Hi

 

 

b050

Selection of the non stop operation

00(Disabled)/01(Enabled stop)/02(Enabled restart)

00

00

00

-

X

 

X

 

 

b051

Non stop operarion start voltage setting

0.0 to 1000.0

0.0

0.0

0.0

V

X

 

X

 

 

b052

OV-LAD Stop level of non stop operation setting

0.0 to 1000.0

0.0

0.0

0.0

V

X

 

X

 

 

b053

Deceleration time of non stop operation setting

0.01 to 3000

1.0

1.0

1.0

sec

X

 

X

 

 

b054

Frequency width of quick deceleration setting

0.0 to 10.0

0.0

0.0

0.0

Hz

X

 

X

 

 

b055

DC bus AVR P-gain

0.2 to 5.0

0.2

0.2

0.2

-

X

 

X

 

 

b056

DC bus AVR I-time

0.0 to 150.0

0.2

0.2

0.2

sec

X

 

X

 

 

b080

[AM] terminal analog meter adjustment

0. to 255.

100.

100.

100.

-

 

 

 

 

 

b082

Start frequency adjustment

0.5 to 9.9

0.5

0.5

0.5

Hz

X

 

 

 

 

b083

Carrier frequency setting

2.0 to 12.0

3.0

3.0

3.0

kHz

X

 

X

 

 

b084

Initialization mode (parameters or trip history)

00(Trip history clear)/01(Parameter initialization)/

00

00

00

-

X

 

X

 

 

02(Trip history clear and parameter initialization)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b085

Country code for initialization

00(JP)/01(CE)/02(US)

01

02

00

-

X

 

X

 

 

b086

Frequency scaling conversion factor

0.1 to 99.9

1.0

1.0

1.0

-

 

 

 

Others

 

b087

STOP key enable

00(Enable)/01(Disable)

00

00

00

-

X

 

 

 

 

b088

Restart mode after FRS

00(Restart from 0Hz)/01(Restart with frequency detection)

00

00

00

-

X

 

 

 

 

 

 

01(Output frequency)/02(Output current)/03(Rotation direction)/

 

 

 

 

 

 

 

 

 

b089

Monitor display select for networked inverter

04(PV, PID feedback)/05(Input terminal status)/

01

01

01

-

 

 

 

 

 

 

 

06(Output terminal status)/07(Scaled output frequency)

 

 

 

 

 

 

 

 

 

b091

Stop mode selection

00(Deceleration and stop)/01(Free-run stop)

00

00

00

-

X

 

X

 

 

b092

Cooling fan control (see note below)

00(Always ON)/01(ON during RUN, OFF during STOP)/

00

00

00

-

X

 

X

 

 

02(Temperature controlled)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b130

Over-voltage LADSTOP enable

00(Disable)/01(Enable)

00

00

00

-

X

 

 

 

 

b131

Over-voltage LADSTOP level

330 to 395V/660 to 790V

380/760

380/760

380/760

V

 

 

 

 

 

b133

DC bus AVR selection

00(Disabled)/01(Enabled)

00

00

00

-

X

 

 

 

 

b134

Threshold voltage of DC bus AVR setting

330 to 395V/660 to 790V

380/760

380/760

380/760

V

X

 

 

 

 

b140

Over-current trip suppression

00(Disable)/01(Enable)

01

01

01

-

X

 

 

 

 

b150

Carrier mode

00(Disable)/01(Enable)

00

00

00

-

X

 

 

 

 

b151

Quick start enable

00(Disable)/01(Enable)

00

00

00

-

 

 

 

C Group: Intelligent terminal functions

 

 

 

 

[X:: NotAllowedallowed ]

 

 

 

 

 

Default

 

 

Run mode

Function Code

 

Name

Range

-EF(CE) -U(UL)

-R(JP)

Unit

 

edit

 

 

 

 

 

Lo

Hi

 

C001

Terminal [1] function

00(FW:Forward), 01(RV:Reverse), 02-05(CF1-CF4:Multispeed command),

00

00

00

-

X

X

 

C201

Terminal [1] function, 2nd motor

06(JG:Jogging), 07(DB:External DC braking), 08(SET:Second motor constants

00

00

00

X

X

 

 

 

C002

Terminal [2] function

setting), 09(2CH:Second accel./decel.), 11(FRS:Free-run stop), 12(EXT:External trip),

01

01

01

-

X

X

 

C202

Terminal [2] function, 2nd motor

13(USP:Unattended start protection), 15(SFT:Software lock), 16(AT:Analog input

01

01

01

X

X

 

 

 

C003

Terminal [3] function

selection), 18(RS:Reset), 19(PTC:Thermistor input), 20(STA:3-wire start),

02

16

02

 

X

X

 

21(STP:3-wire stop), 22(F/R:3-wire fwd./rev.), 23(PID:PID On/Off), 24(PIDC:PID

-

Intelligent input

C203

Terminal [3] function, 2nd motor

02

16

02

X

X

reset), 27(UP:Remote-controlled accel.), 28(DWN:Remote-controlled decel.),

 

terminal

C004

Terminal [4] function

03

13

03

 

X

X

29(UDC:Remote-controlled data clearing), 31(OPE:Operator control),

-

 

C204

Terminal [4] function, 2nd motor

03

13

03

X

X

 

50(ADD: Frequency setpoint), 51(F-TM: Force terminal enable), 52(RDY: Quick Start

 

 

C005

Terminal [5] function

Enable), 53(S-ST: Special-Set (select) 2nd Motor Data), 64(EMR:Safety stop),

18

18

18

-

X

X

 

C205

Terminal [5] function, 2nd motor

255(NO:Not selected)

18

18

18

X

X

 

 

 

C011-

Terminal [1] to [5] active state

00(NO)/01(NC)

00

00*

00

-

X

X

 

C015

 

 

 

 

 

 

 

 

 

 

 

 

00(RUN:run signal), 01(FA1:Frequency arrival type 1 - constant speed),

 

 

 

 

 

 

 

 

 

02(FA2:Frequency arrival type 2 - over-frequency), 03(OL:overload

 

 

 

 

 

 

 

C021

Terminal [11] function

advance notice signal), 04(OD:Output deviation for PID control),

01

01

01

-

X

X

 

05(AL:alarm signal), 06(DC:Wire brake detect on analog input),

 

 

 

 

 

 

 

 

 

 

 

 

07(FBV: Feedback voltage comparison), 08(NDc: Network

 

 

 

 

 

 

 

 

 

Disconnection), 09(LOG: Logic operation result), 10(ODC: Option Card

 

 

 

 

 

 

 

C026

Alarm relay function

Detection Signal), 43(LOC:Low load detection)

05

05

05

-

X

X

 

 

 

C028

[AM] signal selection

00(Output frequency)/01(Output current)

00

00

00

-

X

 

 

C031

Terminal [11] active state

00(NO)/01(NC)

00

00

00

-

X

X

Intelligent input

C036

Alarm relay active state

00(NO)/01(NC)

01

01

01

-

X

X

terminal

C038

Output mode of low load detection signal

00(Disabled)/01(During acceleration, deceleration and constant

01

01

01

-

X

 

 

speed)/02(During constant speed only)

 

 

 

 

 

 

 

 

 

 

 

C039

Low load detection level

0.0 to 2.0*Rated current

 

 

 

 

X

 

 

C041

Overload level setting

0.0*Rated current to 2.0*Rated current

Rated current

A

X

 

 

C241

Overload level setting, 2nd motor

 

 

 

 

X

 

 

 

 

 

 

 

 

 

C042

Frequency arrival setting for acceleration

0.0 to 400.0

0.0

0.0

0.0

Hz

X

 

 

C043

Frequency arrival setting for deceleration

0.0 to 400.0

0.0

0.0

0.0

Hz

X

 

 

C044

PID deviation level setting

0.0 to 100.0

3.0

3.0

3.0

%

X

 

 

C052

Feedback comparison upper level

0.0 to 100.0

100

100

100

%

X

 

 

C053

Feedback comparison lower level

0.0 to 100.0

0.0

0.0

0.0

%

X

 

 

C070

SELECTION OF OPE/MODBUS

02(OPE or option)/03(485)

02

02

02

-

X

 

 

C071

Communication speed selection

04(4800bps)/05(9600bps)/06(19200bps)

06

04

04

-

X

 

 

C072

Node allocation

1. to 32.

1.

1.

1.

-

X

 

 

C074

Communication parity selection

00(No parity)/01(Even parity)/02(Odd parity)

00

00

00

-

X

 

Serial communication

C075

Communication stop bit selection

1(1-bit)/2(2-bit)

1

1

1

bit

X

 

 

C076

Communication error mode

00(Trip)/01(Trip after deceleration stop)/02(Disable)/

02

02

02

-

X

 

 

03(FRS)/04(Deceleration stop)

 

 

 

 

 

 

 

 

 

 

 

C077

Communication error time

0.00 to 99.99

0.00

0.00

0.00

sec

X

 

 

C078

Communication wait time

0. to 1000.

0.

0.

0.

msec

X

 

 

C081

[O] input span calibration

0. to 200.

100.

100.

100.

%

 

 

Analog meter setting

C082

[OI] input span calibration

0. to 200.

100.

100.

100.

%

 

 

 

C086

[AM] terminal offset tuning

0.0 to 10.0

0.0

0.0

0.0

V

 

 

 

C091

Reserved (for factory adjustment)

00 (must not be changed)

00

00

00

-

 

 

 

C101

Up/Down memory mode selection

00(Clear last frequency)/01(Keep last frequency adjusted by UP/DWN)

00

00

00

-

X

 

 

 

 

00(Cancel trip state at input signal ON transition)/ 01(Cancel trip state

 

 

 

 

 

 

 

C102

Reset mode selection

at signal OFF transition)/

00

00

00

-

X

 

 

 

 

02(Cancel trip state at input signal ON transition)

 

 

 

 

 

 

Others

C141

Input A select for logic output 1

00(RUN)/01(FA1)/02(FA2)/03(OL)/04(OD)

00

00

00

-

X

X

C142

Input A select for logic output 2

05(AL)/06(Dc)/07(FBV)/08(NDc)/10(ODc)/43(LOC)

01

01

01

-

X

X

 

 

C143

Logic function select

00(AND)/01(OR)/02(XOR)

00

00

00

-

X

X

 

C144

ON delay time, output terminal 11

0.0 to 100.0

0.0

0.0

0.0

sec

X

 

 

C145

OFF delay time, output terminal 11

0.0 to 100.0

0.0

0.0

0.0

sec

X

 

 

C148

ON delay time, relay

0.0 to 100.0

0.0

0.0

0.0

sec

X

 

 

C149

OFF delay time, relay

0.0 to 100.0

0.0

0.0

0.0

sec

X

 

Note: C014: 01 for UL version.

9

Page 10
Image 10
Hitachi X200 manual Group Intelligent terminal functions

X200 specifications

The Hitachi X200 series is a line of cutting-edge industrial drives designed to enhance operational efficiency and performance across various applications. Developed with advanced technologies, the X200 drives are geared toward providing seamless integration, superior control, and robust reliability in manufacturing environments.

One of the standout features of the Hitachi X200 is its exceptional control capabilities. The drive employs vector control technology, enabling precise and efficient motor control across a range of speeds. This allows users to achieve optimal performance in applications that require a high level of accuracy and responsiveness. The built-in auto-tuning function simplifies the setup process, adjusting parameters automatically to ensure that the drive operates at its best.

Another key characteristic of the X200 series is its energy efficiency. The drives are designed to minimize energy consumption while maximizing output. With features like energy-saving mode and advanced power management, operators can significantly reduce operational costs. This focus on sustainability is becoming increasingly important as industries strive to meet environmental regulations and improve their carbon footprint.

The X200 series also showcases robust communication capabilities. It supports multiple communication protocols, including Modbus, Profibus, and Ethernet/IP. This flexibility ensures that users can easily integrate the drives into existing automation systems and communicate seamlessly with other devices. Additionally, the drive supports remote monitoring and control, allowing for real-time performance tracking and adjustments from anywhere.

Reliability is paramount in industrial settings, and the Hitachi X200 does not disappoint. It is built with high-quality components that ensure durability and longevity even in harsh operating conditions. The drives have a wide operational temperature range and are designed to withstand vibrations, making them suitable for challenging environments.

Furthermore, the X200 series comes equipped with advanced safety features, including built-in motor overload protection and fault diagnosis capabilities. This ensures that any potential issues are identified promptly, minimizing downtime and improving overall reliability.

In conclusion, the Hitachi X200 series offers a comprehensive solution for industries looking to enhance their motor control and automation capabilities. With its advanced control technologies, energy efficiency, robust communication options, and high reliability, the X200 drives stand out as a top choice for modern industrial applications. These features combine to deliver not just performance but also a pathway toward greater operational efficiency and sustainability.