Function List

The parameter tables in this chapter have a column titled "Run Mode Edit." An Ex mark x means the parameter cannot be edited; a Check mark means the parameter can be edited. The table example to the right contains two adjacent marks "x ". These two marks (that can

also be "xx" or " ") correspond to low-access or high-access levels to Run Mode edits (note Lo and Hi in column heading).

[: Allowed ]

Monitoring and main profile parametersX: Not allowed

Function Code

 

Name

 

 

Range

Default

Unit

Run mode edit

 

 

 

Lo

Hi

 

 

 

 

 

 

 

 

 

 

 

d001

Output frequency monitor

0.0 to 400.0

 

 

 

 

-

Hz

-

-

 

d002

Output current monitor

0.0 to 999.9

 

 

 

 

-

A

-

-

 

d003

Rotation direction monitor

F(Forward)/o(Stop)/r(Reverse)

 

 

-

-

-

-

 

d004

Process variable, PID feedback monitor

0.00 to 99.99/100.0 to 999.9/1000. to 9999.

-

-

-

-

 

d005

Intelligent input terminal status

 

 

ON

e.g. :￿1,2￿ : ON

-

-

-

-

 

5 4

3 2

1 OFF

￿

3,4,5￿: OFF

 

d006

Intelligent output terminal status

 

 

ON

e.g. :￿11￿ : ON

-

-

-

-

 

 

AL

OFF

￿

AL￿ : OFF

 

 

 

 

11

 

 

 

 

 

 

 

d007

Scaled output frequency monitor

0.00 to 99.99/100.0 to 999.9/1000. to 9999./1000 to 9999(10000 to 99999)

-

-

-

-

Monitor

d013

Output voltage monitor

0.0 to 600.0

 

 

 

 

-

V

-

-

 

d016

Cumulative operation RUN time monitor

0. to 9999./1000 to 9999/

100 to

999 (10000 to 99900)

-

hr

-

-

 

d017

Cumulative power-on time monitor

0. to 9999./1000 to 9999

 

 

 

-

hr

-

-

 

d018

Cooling fin temperature monitor

0.0 to 200.0

 

 

 

 

-

˚C

-

-

 

d080

Trip counter

0. to 9999.

 

 

 

 

-

events

-

-

 

d081

Trip monitor 1

 

 

 

 

 

-

-

-

-

 

d082

Trip monitor 2

Displays trip event information

 

 

-

-

-

-

 

d083

Trip monitor 3

 

 

 

 

 

-

-

-

-

 

d102

DC bus voltage monitor

0.0 to 999.9

 

 

 

 

-

V

-

-

 

d104

Electronic themal monitor

0.0 to 100.0

 

 

 

 

-

%

-

-

 

F001

Output frequency setting

0.0/start freq. to 400.0

 

 

 

0.0

Hz

 

 

 

F002

Acceleration time (1) setting

0.01 to 99.99/100.0 to 999.9/1000. to 3000.

10.0

sec

 

 

Main Profile

F202

Acceleration time (2) setting

0.01 to 99.99/100.0 to 999.9/1000. to 3000.

10.0

sec

 

 

Parameters

F003

Deceleration time (1) setting

0.01 to 99.99/100.0 to 999.9/1000. to 3000.

10.0

sec

 

 

 

F203

Deceleration time (2) setting

0.01 to 99.99/100.0 to 999.9/1000. to 3000.

10.0

sec

 

 

 

F004

Keypad Run key routing

00(Forward)/01(Reverse)

 

 

 

00

-

X

X

 

A--

A Group: Standard functions

 

 

 

 

 

 

 

 

 

 

b--

b Group: Fine-tuning functions

 

 

 

 

 

 

 

 

 

Expanded functions

C--

C Group: Intelligent terminal functions

 

 

 

 

 

 

 

 

 

 

H--

H Group: Motor constants functions

 

 

 

 

 

 

 

 

 

 

P--

P Group: Expansion Card Functions

 

 

 

 

 

 

 

 

 

A Group: Standard functions

[X:: AllowedNot allowed ]

 

 

 

 

 

Default

 

 

Run mode

Function Code

 

Name

Range

-EF(CE)

-U(UL)

-R(JP)

Unit

 

edit

 

 

 

 

 

Lo

Hi

 

A001

Frequency source setting

00(Keypad potentiometer)/01(Control terminal)/

01

00

00

-

X

X

 

A201

Frequency source setting, 2nd motor

02(Function F001 setting)/03(RS485)/10(Calculation result)

01

00

00

-

X

X

 

A002

Run command source setting

01(Control terminal)/02(Run key on keypad)/03(RS485)

01

02

02

-

X

X

 

A202

Run command source setting, 2nd motor

01

02

02

-

X

X

Basic setting

 

A003

Base frequency setting

30 to maximum freq.

50.

60.

60.

Hz

X

X

 

 

A203

Base frequency setting, 2nd motor

30 to maximum freq.

50.

60.

60.

Hz

X

X

 

A004

Maximum frequency setting

30 to 400

50.

60.

60.

Hz

X

X

 

A204

Maximum frequency setting, 2nd motor

30 to 400

50.

60.

60.

Hz

X

X

 

A005

[AT] selection

02(O/VR)/03(OI/VR)/04(O)/05(OI)

02

02

02

-

X

 

 

A011

[O]-[L] input active range start frequency

0.0 to maximum freq.

0.0

0.0

0.0

Hz

X

 

 

A012

[O]-[L] input active range end frequency

0.0 to maximum freq.

0.0

0.0

0.0

Hz

X

 

Analog input setting

A013

[O]-[L] input active range start voltage

0 to 100

0.

0.

0.

%

X

 

 

A014

[O]-[L] input active range end voltage

0 to 100

100.

100.

100.

%

X

 

 

A015

[O]-[L] input start frequency enable

00(use set value)/01(use 0 Hz)

01

01

01

-

X

 

 

A016

External frequency filter time constant

1 to 17

8.

8.

8.

-

X

 

 

A020

Multi-speed frequency setting (0)

 

0.0

0.0

0.0

Hz

 

 

 

A220

Multi-speed frequency (2nd), setting 2nd motor

 

0.0

0.0

0.0

Hz

 

 

 

A021

Multi-speed frequency setting (1)

 

0.0

0.0

5.0

Hz

 

 

 

A022

Multi-speed frequency setting (2)

 

0.0

0.0

10.0

Hz

 

 

 

A023

Multi-speed frequency setting (3)

 

0.0

0.0

15.0

Hz

 

 

 

A024

Multi-speed frequency setting (4)

0.0/start freq. to maximum freq.

0.0

0.0

20.0

Hz

 

 

Multi-speed and

A025

Multi-speed frequency setting (5)

0.0

0.0

30.0

Hz

 

 

 

 

 

jogging

A026

Multi-speed frequency setting (6)

 

0.0

0.0

40.0

Hz

 

 

 

A027

Multi-speed frequency setting (7)

 

0.0

0.0

50.0

Hz

 

 

 

A028

Multi-speed frequency setting (8)

 

0.0

0.0

60.0

Hz

 

 

 

A029-

Multi-speed frequency setting (9-15)

 

0.0

0.0

0.0

Hz

 

 

 

A035

 

 

 

 

 

 

 

 

 

 

 

 

 

A038

Jog frequency setting

0.00/start freq. to 9.99

100.

100.

100.

Hz

 

 

 

A039

Jog stop mode

00(free-run stop)/01(deceleration and stop)/02 (DC braking)

00

00

00

-

X

 

 

A041

Torque boost select

00(Manual)/01(Automatic)

00

00

00

-

X

X

 

A241

Torque boost select 2nd motor

00(Manual)/01(Automatic)

00

00

00

-

X

X

 

A042

Manual torque boost value

0.0 to 20.0

1.8

1.8

1.8

%

 

 

 

A242

Manual torque boost value, 2nd motor

0.0 to 20.0

0.0

0.0

0.0

%

 

 

V/f

A043

Manual torque boost frequency adjustment

0.0 to 50.0

10.0

10.0

10.0

%

 

 

Characteristic

A243

Manual torque boost frequency adjustment, 2nd motor

0.0 to 50.0

0.0

0.0

0.0

%

 

 

 

A044

V/f characteristic curve selection

00(VC)/01(Reduced torque)/06 (Reduced torque 1)

00

00

00

-

X

X

 

A244

V/f characteristic curve selection, 2nd motor

00(VC)/01(Reduced torque)/06 (Reduced torque 1)

00

00

00

-

X

X

 

A045

V/f gain setting

20 to 100

100.

100.

100.

%

 

 

 

A245

V/f gain setting, 2nd motor

20 to 100

100.

100.

100.

%

 

 

 

A051

DC braking enable

00(Disable)/01(Enable)/02(Frequency detection)

100.

100.

00

-

X

 

 

A052

DC braking frequency setting

0.0 to 60.0

0.5

0.5

0.5

Hz

X

 

DC braking

A053

DC braking wait time

0.0 to 5.0

0.0

0.0

0.0

sec

X

 

A054

DC braking force during deceleration

0. to 100.

0.

0.

0.

Hz

X

 

 

 

 

A055

DC braking time for deceleration

0.0 to 60.0

0.0

0.0

0.0

sec

X

 

 

A056

DC braking / edge or level detection for [DB] input

00(Edge)/01(Level)

01

01

01

-

X

 

7

Page 8
Image 8
Hitachi X200 manual Function List, Monitoring and main profile parametersX Not allowed, Group Standard functions

X200 specifications

The Hitachi X200 series is a line of cutting-edge industrial drives designed to enhance operational efficiency and performance across various applications. Developed with advanced technologies, the X200 drives are geared toward providing seamless integration, superior control, and robust reliability in manufacturing environments.

One of the standout features of the Hitachi X200 is its exceptional control capabilities. The drive employs vector control technology, enabling precise and efficient motor control across a range of speeds. This allows users to achieve optimal performance in applications that require a high level of accuracy and responsiveness. The built-in auto-tuning function simplifies the setup process, adjusting parameters automatically to ensure that the drive operates at its best.

Another key characteristic of the X200 series is its energy efficiency. The drives are designed to minimize energy consumption while maximizing output. With features like energy-saving mode and advanced power management, operators can significantly reduce operational costs. This focus on sustainability is becoming increasingly important as industries strive to meet environmental regulations and improve their carbon footprint.

The X200 series also showcases robust communication capabilities. It supports multiple communication protocols, including Modbus, Profibus, and Ethernet/IP. This flexibility ensures that users can easily integrate the drives into existing automation systems and communicate seamlessly with other devices. Additionally, the drive supports remote monitoring and control, allowing for real-time performance tracking and adjustments from anywhere.

Reliability is paramount in industrial settings, and the Hitachi X200 does not disappoint. It is built with high-quality components that ensure durability and longevity even in harsh operating conditions. The drives have a wide operational temperature range and are designed to withstand vibrations, making them suitable for challenging environments.

Furthermore, the X200 series comes equipped with advanced safety features, including built-in motor overload protection and fault diagnosis capabilities. This ensures that any potential issues are identified promptly, minimizing downtime and improving overall reliability.

In conclusion, the Hitachi X200 series offers a comprehensive solution for industries looking to enhance their motor control and automation capabilities. With its advanced control technologies, energy efficiency, robust communication options, and high reliability, the X200 drives stand out as a top choice for modern industrial applications. These features combine to deliver not just performance but also a pathway toward greater operational efficiency and sustainability.