4-3. Grounding Generator When Supplying Building Systems

1 2

GND/PE

Use ground device as stated in electrical codes.

23

1Equipment Grounding Terminal

2Grounding Cable

Use #10 AWG or larger insulated copper wire.

3 Ground Device

YGround generator to sys- tem earth ground if supply- ing power to a premises (home, shop, farm) wiring system.

800 576-B

4-4. Engine Prestart Checks

1/2 in

 

(13 mm)

Full

 

Gasoline

 

1

Open

Closed

.Always close fuel valve after

stopping unit. Moving unit with fuel valve open may cause carburetor flooding and make starting difficult.

Check all fluids daily. Engine must be cold and on a level surface. Unit is shipped with 10W30 engine oil.

Engine stops if oil level gets too low.

1Fuel Valve Open valve.

.Close fuel valve before moving

unit or carburetor may flood and make starting difficult.

Fuel

Add fresh fuel before starting engine the first time (see mainte- nance label for specifications). Fill fuel tank up to 1/2 in. (13 mm) from top to allow room for expansion. Check fuel level on a cold engine before use each day.

Oil

After fueling, check oil with unit on level surface. If oil reservoir is not full, add oil until oil nearly overflows at oil fill (see maintenance label).

.This unit has a low oil level

shutdown switch to prevent starting an engine that is low on oil. However, some conditions may cause engine damage be- fore the engine shuts down. Check oil level often and do not use the low oil level shutdown system to monitor oil level.

.To improve cold weather start- ing, use correct grade oil for cold weather (see engine own- er’s manual).