2-8. 115 Volts AC Duplex Receptacle

Y Turn Off power before con- necting to receptacle.

1 115 V AC Receptacle

Receptacle is protected from over- load by circuit breaker CB1 (see Section 4-2).

Power output is shared between this receptacle and the Remote 14 receptacle (see Section 2-7).

1

Ref. ST-152 973-A

2-9. Electrical Service Guide

 

 

60 Hz

 

 

50 Hz

 

 

 

 

 

 

 

 

 

Input Voltage

200

230

460

575

220

380

415

 

 

 

 

 

 

 

 

Input Amperes At Rated Output

105

91

46

36

88

51

47

 

 

 

 

 

 

 

 

Max Recommended Standard Fuse Or Circuit Breaker Rating In

 

 

 

 

 

 

 

Amperes

 

 

 

 

 

 

 

Circuit Breaker1 , Time-Delay 2

125

110

50

45

110

60

50

Normal Operating 3

150

125

70

50

125

80

70

Min Input Conductor Size In AWG/Kcmil

4

6

8

10

6

8

8

 

 

 

 

 

 

 

 

Max Recommended Input Conductor Length In Feet (Meters)

116

103

271

284

99

194

232

(35)

(31)

(83)

(87)

(30)

(59)

(71)

 

 

 

 

 

 

 

 

 

Min Grounding Conductor Size In AWG/Kcmil

6

6

8

10

6

8

8

 

 

 

 

 

 

 

 

Reference: 1999 National Electrical Code (NEC)

1Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.

2“Time-Delay” fuses are UL class “RK5” .

3“Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).

OM-318 Page 13