3-5. Electrical Service Guide

YCAUTION: INCORRECT INPUT POWER can damage this welding power source. This welding pow- er source requires a CONTINUOUS supply of 60 Hz (+10%) power at +10% of rated input voltage. Do not use a generator with automatic idle device (that idles engine when no load is sensed) to supply input power to this welding power source.

NOTE

Actual input voltage should not exceed ± 10% of indicated required input voltage. If actual input voltage is outside of this range, output may not be available.

 

60 Hz Three Phase

60 Hz Single

 

 

Phase

 

 

 

 

 

 

 

 

 

 

 

 

Input Voltage

230

460

575

230

 

460

 

 

 

 

 

 

 

Input Amperes At Rated Output

31

15

12

53

 

27

 

 

 

 

 

 

 

Max Recommended Standard Fuse Rating In Amperes 1

 

 

 

 

 

 

Time-Delay 2

35

15

15

60

 

30

Normal Operating 3

45

20

20

80

 

40

 

 

 

 

 

 

 

Min Input Conductor Size In AWG/Kcmil

10

14

14

8

 

10

 

 

 

 

 

 

 

Max Recommended Input Conductor Length In Feet (Meters)

112

175

274

85

 

224

(34)

(53)

(83)

(26)

 

(68)

 

 

 

 

 

 

 

 

 

Min Grounding Conductor Size In AWG/Kcmil

10

14

14

8

 

10

 

 

 

 

 

 

 

Reference: 1999 National Electrical Code (NEC)

1Consult factory for circuit breaker applications.

2“Time-Delay” fuses are UL class “RK5” .

3“Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).