3-5. Electrical Service Guide
YCAUTION: INCORRECT INPUT POWER can damage this welding power source. This welding pow- er source requires a CONTINUOUS supply of 60 Hz (+10%) power at +10% of rated input voltage. Do not use a generator with automatic idle device (that idles engine when no load is sensed) to supply input power to this welding power source.
NOTE
Actual input voltage should not exceed ± 10% of indicated required input voltage. If actual input voltage is outside of this range, output may not be available.
| 60 Hz Three Phase | 60 Hz Single | ||||
|
| Phase | ||||
|
|
|
|
| ||
|
|
|
|
|
|
|
Input Voltage | 230 | 460 | 575 | 230 |
| 460 |
|
|
|
|
|
|
|
Input Amperes At Rated Output | 31 | 15 | 12 | 53 |
| 27 |
|
|
|
|
|
|
|
Max Recommended Standard Fuse Rating In Amperes 1 |
|
|
|
|
|
|
35 | 15 | 15 | 60 |
| 30 | |
Normal Operating 3 | 45 | 20 | 20 | 80 |
| 40 |
|
|
|
|
|
|
|
Min Input Conductor Size In AWG/Kcmil | 10 | 14 | 14 | 8 |
| 10 |
|
|
|
|
|
|
|
Max Recommended Input Conductor Length In Feet (Meters) | 112 | 175 | 274 | 85 |
| 224 |
(34) | (53) | (83) | (26) |
| (68) | |
|
| |||||
|
|
|
|
|
|
|
Min Grounding Conductor Size In AWG/Kcmil | 10 | 14 | 14 | 8 |
| 10 |
|
|
|
|
|
|
|
Reference: 1999 National Electrical Code (NEC)
1Consult factory for circuit breaker applications.
2
3“Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).