04 Calibration offset
This item is used to raise or lower the current temperature reading by 1 degree Fahrenheit or 1/2 degree Celsius. If this item is set to 30, no change will be made. Each digit below 30 will lower to temperature, and each digit above 30 will raise the temperature.
(1 = “- 29” to 59 = “+ 29” temperature units; 30 = No change)
The default setting is 30.
05 Cool setpoint limit
This item is used to limit the temperature setting in cool mode. The desired cool setting can never be set below this setting.
The default setting is 51.
06 Heat setpoint limit
This item is used to limit the temperature setting in heat mode. The desired heat setting can never be set above this setting.
The default setting is 91.
07Not used
08Not used
09Cooling anticipator
This item adjusts the tendency of the thermostat to run the cooling system to refresh and dehumidify the air before the temperature rises to the desired cool setting. A setting of 0 will disable this feature.
0 | No anticipation |
Normal anticipation | |
10 | Maximum anticipation |
The recommended setting for most forced air cooling systems is 4. A lower number will decrease the tendency to run the cooling system below the cooling setting. A lower setting of 2 or 3 may be desired in dry climates.
The default setting is 4.
10