Home Automation RC-80BZ installation instructions Description, Installation, Location

Models: RC-80BZ

1 16
Download 16 pages 11.07 Kb
Page 1
Image 1
RC-80BZ Single Stage Heat/Cool

RC-80BZ Single Stage Heat/Cool

Thermostat Installation Instructions

DESCRIPTION

The RC-80BZ is a precision digital thermostat designed for 24 VAC single stage heating and cooling systems. It has the capability of being controlled both locally and by remote control over a Z-Wave network. It offers programmability, stand-alone operation, and communications with automation systems, utility control systems, or personal computers over a Z-Wave network. The RC-80ZB is equipped with a “cool blue” backlight display.

Electrical rating:

24 V; 3 A; 50/60 Hz

Maximum current:

2 A on any circuit, 3 A total

Thermostat operating current:

less than 15 mA

The following requirements must be observed for installation in Europe: CE

1.This equipment must be installed in accordance with National wiring rules for the country in which it is installed.

2.Fuses must be replaced only with IEC rated components.

3.All product labels, instructions and markings relating to safety must be translated to a language, which is acceptable in the country in which this equipment is to be installed.

INSTALLATION

Before installing this thermostat:

1.Read all of the installation instructions carefully.

2.Read the Owner's Manual carefully.

3.Ensure that this product is suitable for your application.

4.Ensure that wiring complies with all codes and ordinances.

5.Disconnect power to the control transformer to prevent electrical shock and damage to equipment.

6.Select an appropriate location to ensure an accurate temperature reading.

Location

When replacing an existing thermostat, install the RC-80BZ in the same location. If the existing location doesn't meet the following criteria, choose a new location to mount the RC-80BZ. When choosing a location for the thermostat:

1.Ensure that the thermostat is mounted 5 feet above the floor and is at least 2 feet from an outdoor wall.

2.Ensure that the thermostat is located in an area where there is adequate air circulation.

3.Do not mount in the path of direct sunlight or of radiant heat generated by appliances.

4.Do not mount behind an outdoor wall, near a fireplace, or in the path of any air ducts.

Document Number 13I00-60 / Rev A / May, 2007