Home Automation RC-80BZ installation instructions Troubleshooting Tips, Symptom, Action To Take

Models: RC-80BZ

1 16
Download 16 pages 11.07 Kb
Page 16
Image 16
TROUBLESHOOTING TIPS

TROUBLESHOOTING TIPS

SYMPTOM

 

ACTION TO TAKE

Thermostat Dead

 

1.

Check power to the thermostat

 

 

2.

Check wiring diagrams

 

 

3.

Check thermostat temperature sensor

 

Thermostat will not operate with a damaged temperature sensor.

SYMPTOM

 

ACTION TO TAKE

Fan, Heat, Or Cool

1.

Check for break in G, W, or Y wire

Inoperative

2.

Allow minimum off time to pass

 

3.

Check system options for correct settings

 

4.

Remote system is overriding thermostat

"REMOTE" is

displayed when system is overriding thermostat.

SYMPTOM

 

ACTION TO TAKE

Can't Adjust Temperature

1.

Mode is Off (Select Heat, Cool, or Auto)

 

2.

Check if thermostat keys are disabled

To enable thermostat keys for test, remove jumper.

 

 

 

SYMPTOM

 

ACTION TO TAKE

Control By Remote System

1.

Check Node ID

Not Working

2.

Check communications mode setting

 

34.

Check setup of the remote system

Ensure that all setup items for the thermostat and the remote system

are set to the proper configurations for communication.

SYMPTOM

 

ACTION TO TAKE

Temperature Reading

1.

Allow 30 minutes for thermostat to adjust to room

Incorrect

 

temperature

 

2.

Adjust calibration offset

 

3.

Change setup option to display oF or oC

After installation, allow the thermostat up to 30 minutes for an accurate temperature reading.

SYMPTOM

ACTION TO TAKE

Display Problem

1. Disconnect power to the thermostat. Reconnect, then

 

observe display self-test

For a 5 second period after power is reconnected, all segments of the display should light indicating all thermostat functions.

16

Page 16
Image 16