Homelite UT905011 Electrical, Extension Cord Cable Size, Electric Motor Loads, Current in

Models: UT905011

1 64
Download 64 pages 9.76 Kb
Page 12
Image 12
ELECTRICAL

ELECTRICAL

EXTENSION CORD CABLE SIZE

Refer to the table below to ensure the cable size of the extension cords you use are capable of carrying the required load. Inadequate size cables can cause a voltage drop, which can burn out the appliance and overheat the cord.

Current in

Load in Watts

 

Maximum Allowable Cord Length

 

Amperes

At 120V

At 240V

#8 Wire

#10 Wire

#12 Wire

#14 Wire

#16 Wire

 

 

 

 

 

 

 

 

2.5

  300

  600

 

1000 ft.

600 ft.

375 ft.

250 ft.

 

 

 

 

 

 

 

 

5

  600

1200

 

  500 ft.

300 ft.

200 ft.

125 ft.

 

 

 

 

 

 

 

 

7.5

  900

1800

 

  350 ft.

200 ft.

125 ft.

100 ft.

10

1200

2400

 

  250 ft.

150 ft.

100 ft.

  50 ft.

 

 

 

 

 

 

 

 

15

1800

3600

 

  150 ft.

100 ft.

  65 ft.

 

 

 

 

 

 

 

 

 

20

2400

4800

175 ft.

  125 ft.

  75 ft.

 

 

 

 

 

 

 

 

 

 

25

3000

6000

150 ft.

  100 ft.

 

 

 

 

 

 

 

 

 

 

 

30

3600

7200

125 ft.

  65 ft.

 

 

 

 

 

 

 

 

 

 

 

40

4800

9600

  90 ft.

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRIC MOTOR LOADS

It is characteristic of common electric motors in normal operation to draw up to six times their running current while start- ing. This table may be used to estimate the watts required to start “Code G” electric motors; however, if an electric motor fails to start or reach running speed, turn off the appliance or tool immediately to avoid equipment damage. Always check the requirements of the tool or appliance being used compared to the rated output of the generator.

Motor Size (H.P.)

Running Watts

Watts Required to Start Motor

 

 

 

 

 

Repulsion Induction

Capacitor

 

Split Phase

 

 

 

 

 

 

 

 

 

1/8

  275

  600

  850

 

1200

 

 

 

 

 

 

1/6

  275

  600

  850

 

2050

 

 

 

 

 

 

1/4

  400

  850

1050

 

2400

 

 

 

 

 

 

1/3

  450

  975

1350

 

2700

 

 

 

 

 

 

1/2

  600

1300

1800

 

3600

 

 

 

 

 

 

3/4

  850

1900

2600

 

 

 

 

 

 

 

1

1100

2500

3300

 

 

 

 

 

 

 

CAUTION

Operating voltage and frequency requirement of all electronic equipment should be checked prior to plugging them into this generator. Damage may result if the equipment is not designed to operate within a +/- 10% voltage variation, and +/- 3 hz frequency variation from the generator name plate ratings. To avoid damage, always have an additional load plugged into the generator if solid state equipment (such as a television set) is used. A power line conditioner is recommended for some solid state applications.

GROUND FAULT CIRCUIT INTERRUPTER

See Figure 1.

The 20 amp, 120 volt receptacles on the generator are protect- ed by a Ground Fault Circuit Interrupter (GFCI), which guards against the hazards of ground fault currents. An example of ground fault current is the current that would flow through a

person who is using an appliance with faulty insulation and, at the same time, is in contact with an electrical ground such as a plumbing fixture, wet floor, or earth.

GFCI receptacles do not protect against short circuits, over- loads, or shocks.

The GFCI receptacles can be tested with the TEST and RESET buttons.

To test:

Depress the TEST button. This should cause the Reset button to pop out.

To restore power, depress the RESET button.

Perform this test monthly to ensure proper operation of the GFCI. If the generator is stored outdoors, unprotected from the weather, test the GFCI receptacle before each use.

Page 8 — English
Page 12
Image 12
Homelite UT905011 Electrical, Extension Cord Cable Size, Electric Motor Loads, Ground Fault Circuit Interrupter, Amperes