TAKING CARE OF UNEXPECTED PROBLEMS
GENERATOR PROBLEMS
No Power at the | Possible Cause | Correction |
DC Output Coupler |
|
|
1. Check output | Output indicator is | Check DC load. |
and overload | OFF, and overload | Stop and restart |
indicator. | indicator is ON. | the engine. |
|
| Check the cooling |
|
| air inlet. Stop and |
|
| restart the engine. |
2. Check UPS | Setting different | Turn off the engine |
battery string | voltage connected | switch and set the |
voltage | to the UPS. | voltage selector |
requirement. |
| switch to the same |
|
| battery string |
|
| voltage of the UPS |
|
| (p. 14). |
3. Check the power | Power cord | Make sure |
cord. | connected to UPS | generator positive |
| battery string in | output side of |
| reverse polarity. | coupler is |
|
| connected to |
|
| positive terminal |
|
| of UPS battery |
|
| string. |
4. Take generator | Faulty generator. | Replace or repair |
to an authorized |
| faulty components |
Alphagen |
| as necessary. |
servicing dealer, |
|
|
or refer to shop |
|
|
manual. |
|
|
56