Table 2. F111 Air Volume Specifications for 3 Speed Models (Series 3).

 

 

 

 

Particulates at

Gas, V.O.C. and

Higha

Medium

Low

Model

 

Voltage

0.3 Micron

Odor Control

in cfm

in cfm

in cfm

 

(DOP Test)

Modules (2)

(m3/hr)

(m3/hr)

(m3/hr)

F111A1253W-3S 120 Vac, 60

Hz, 8.5A

95% ASHRAE

N/A

1250

(2120)

800

(1360)

450 (760)

 

 

 

 

 

 

 

 

 

 

 

F111A1063W-3S

120

Vac, 60

Hz, 7.2A

99.97% HEPA

N/A

950

(1610)

775

(1310)

450 (760)

 

 

 

 

 

 

 

 

F111C1073W-3S 120 Vac, 60

Hz, 7.5A

95% ASHRAE

CPZ™ modules

1150 (1950)

825

(1400)

450 (760)

 

 

 

 

 

 

 

 

 

F111C1003W-3S 120 Vac, 60

Hz, 7.0A

99.97% HEPA

CPZ™ modules

825

(1400)

700

(1190)

450 (760)

 

 

 

 

 

 

 

F111C1012W-3S 120 Vac, 60

Hz, 8.0A

95% at 0.3 micron

CPZ™ modules

1125 (1910)

825 (1400)

450 (760)

 

 

 

 

 

 

 

 

 

 

F111A2253W-3S

230

Vac, 50

Hz, 4.2A

95% ASHRAE

N/A

1125 (1910)

700

(1190)

475 (810)

 

 

 

 

 

 

 

 

 

 

 

F111A2007W-3S

230

Vac, 50

Hz, 3.5A

99.97% HEPA

N/A

900

(1530)

600

(1020)

400 (680)

 

 

 

 

 

 

 

 

 

F111C2073W-3S 230 Vac, 50

Hz, 4.0A

95% ASHRAE

CPZ™ modules

1025

(1740)

675

(1150)

450 (760)

 

 

 

 

 

 

 

 

 

F111C2003W-3S 230 Vac, 50

Hz, 3.2A

99.97% HEPA

CPZ™ modules

825

(1400)

550

(930)

375 (640)

 

 

 

 

 

 

 

 

F111C1053W-3S 230

Vac, 50

Hz, 3.5A

95% at 0.3 micron CPZ™ modules

950

(1610)

625 (1060)

425 (720)

aSame for Single Speed Models (Series 1 & 2).

.

 

 

 

Accessories:

TOP VIEW

Black Color Grill

Remote 3-Speed Wall Switch

 

 

 

 

 

 

Manual background3/8 X 16 INTERNAL THREAD (4)

Replacement Parts See Parts List, Table 5.

PLANNING THE INSTALLATION

48 (1219)

Manual background 46-3/4 (1187) Manual background

POWER CONNECTION

POINT

17-1/4

(438)

4-1/2

(114)

Manual background 24 (610) Manual background

Manual background 22-1/2 (572) Manual background

CEILING

LINE

M11996A

The number of F111 (series 1,2,3) air cleaners that are needed is determined by taking into account the number of occupants and the volume of the space. Type of contamination, outdoor air quality and use of the area are also factors. Refer to Table 3 for general guidelines when determining how many air cleaners are needed.

EXAMPLE: One air cleaner can provide 2.5 air changes per hour in a 24,000 cubic feet (720 cubic meters) no smoking area. Table 3 suggests two air cleaners for a 24,000 cubic feet area because most areas

Fig. 1. Approximate dimensions of F111

(Series 1,2,3) in in. (mm).

Installation Weight:

Approximately 115 lb to 155 lb (kg) depending on the filter configuration. Refer to Table 3.

Table 3. Sorbent Module Weight.

Media

Weight in lb (kg)

CPZ™ modules (2)

43 (20)

 

 

Sound Level at 3.3 ft (1m):

Low speed: 53 dBA (3 speed models only).

Medium speed: 57 dBA (3 speed models only)

High speed: 61 dBA.

Grille Type: Perforated metal.

Mounting: Recesses into opening on the ceiling.

Approvals:

Underwriters Laboratories Inc.: Listed.

Canadian Standards Association: Listed.

have contaminants that require more units to provide quality air.

If any questions should arise concerning determining the number of air cleaners needed for an area, consult your distributor or local Honeywell Commercial Air Cleaner Distributor.

Table 4. Determining the Minimum Number of

Air Cleaners Needed for a Space.

Space Volume

 

Minimum

(L x W x H) in Cubic

Number of

Number of Air

Feet (Cubic Meter)

Persons Present

Cleaners

12000 to 18000

30 to 60

1

(360 to 540)

 

 

 

 

 

18001 to 35000

61 to 90

2

(540 to 1050)

 

 

 

 

 

3

68-0198-2

Page 3
Image 3
Honeywell F111 Series 3 specifications Planning The Installation