F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER
Table 2. F111 Air Volume Specifications for 3 Speed Models (Series 3).
|
|
|
| Particulates at | Gas, V.O.C. and | Higha | Medium | Low | ||
Model |
| Voltage | 0.3 Micron | Odor Control | in cfm | in cfm | in cfm | |||
| (DOP Test) | Modules (2) | (m3/hr) | (m3/hr) | (m3/hr) | |||||
Hz, 8.5A | 95% ASHRAE | N/A | 1250 | (2120) | 800 | (1360) | 450 (760) | |||
|
|
|
|
|
|
|
|
|
|
|
120 | Vac, 60 | Hz, 7.2A | 99.97% HEPA | N/A | 950 | (1610) | 775 | (1310) | 450 (760) | |
|
|
|
|
|
|
|
| |||
Hz, 7.5A | 95% ASHRAE | CPZ™ modules | 1150 (1950) | 825 | (1400) | 450 (760) | ||||
|
|
|
|
|
|
|
|
| ||
Hz, 7.0A | 99.97% HEPA | CPZ™ modules | 825 | (1400) | 700 | (1190) | 450 (760) | |||
|
|
|
|
|
|
| ||||
Hz, 8.0A | 95% at 0.3 micron | CPZ™ modules | 1125 (1910) | 825 (1400) | 450 (760) | |||||
|
|
|
|
|
|
|
|
|
| |
230 | Vac, 50 | Hz, 4.2A | 95% ASHRAE | N/A | 1125 (1910) | 700 | (1190) | 475 (810) | ||
|
|
|
|
|
|
|
|
|
|
|
230 | Vac, 50 | Hz, 3.5A | 99.97% HEPA | N/A | 900 | (1530) | 600 | (1020) | 400 (680) | |
|
|
|
|
|
|
|
|
| ||
Hz, 4.0A | 95% ASHRAE | CPZ™ modules | 1025 | (1740) | 675 | (1150) | 450 (760) | |||
|
|
|
|
|
|
|
|
| ||
Hz, 3.2A | 99.97% HEPA | CPZ™ modules | 825 | (1400) | 550 | (930) | 375 (640) | |||
|
|
|
|
|
|
|
| |||
Vac, 50 | Hz, 3.5A | 95% at 0.3 micron CPZ™ modules | 950 | (1610) | 625 (1060) | 425 (720) |
aSame for Single Speed Models (Series 1 & 2).
.
|
|
| Accessories: | |
TOP VIEW | Black Color Grill | |||
Remote | ||||
|
|
| ||
|
|
|
3/8 X 16 INTERNAL THREAD (4)
Replacement Parts See Parts List, Table 5.
PLANNING THE INSTALLATION
48 (1219)
POWER CONNECTION
POINT
(438)
(114)
24 (610)
CEILING
LINE
M11996A
The number of F111 (series 1,2,3) air cleaners that are needed is determined by taking into account the number of occupants and the volume of the space. Type of contamination, outdoor air quality and use of the area are also factors. Refer to Table 3 for general guidelines when determining how many air cleaners are needed.
EXAMPLE: One air cleaner can provide 2.5 air changes per hour in a 24,000 cubic feet (720 cubic meters) no smoking area. Table 3 suggests two air cleaners for a 24,000 cubic feet area because most areas
Fig. 1. Approximate dimensions of F111
(Series 1,2,3) in in. (mm).
Installation Weight:
Approximately 115 lb to 155 lb (kg) depending on the filter configuration. Refer to Table 3.
Table 3. Sorbent Module Weight.
Media | Weight in lb (kg) |
CPZ™ modules (2) | 43 (20) |
|
|
Sound Level at 3.3 ft (1m):
Low speed: 53 dBA (3 speed models only).
Medium speed: 57 dBA (3 speed models only)
High speed: 61 dBA.
Grille Type: Perforated metal.
Mounting: Recesses into opening on the ceiling.
Approvals:
Underwriters Laboratories Inc.: Listed.
Canadian Standards Association: Listed.
have contaminants that require more units to provide quality air.
If any questions should arise concerning determining the number of air cleaners needed for an area, consult your distributor or local Honeywell Commercial Air Cleaner Distributor.
Table 4. Determining the Minimum Number of
Air Cleaners Needed for a Space.
Space Volume |
| Minimum |
(L x W x H) in Cubic | Number of | Number of Air |
Feet (Cubic Meter) | Persons Present | Cleaners |
12000 to 18000 | 30 to 60 | 1 |
(360 to 540) |
|
|
|
|
|
18001 to 35000 | 61 to 90 | 2 |
(540 to 1050) |
|
|
|
|
|
3 |