![Fig. 5. Fasten cabinet to a structural support.](/images/new-backgrounds/54558/5455811x1.webp)
F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER
TOP OF METAL CABINET
THREADED
ROD
JAM
NUT
CHAIN
EYEBOLT
JAM NUT 3/8 IN. X 16T
HEX BOLT
LOCK
WASHER
CAUTION
• This installation to be performed only by a qualified |
installer. |
• All wiring to comply with local electrical codes. |
• Disconnect power to air cleaner at fuse or breaker |
before beginning work. Failure to do so can result in |
shock hazard endangering equipment and personal |
safety of installer. |
• Only one air cleaner can be connected to a remote |
switch |
OR USING OPTIONAL "Z" BRACKETS
TOP OF METAL CABINET
"Z" BRACKET (4)
NOTE:
FASTEN SECURELY TO STRUCTURAL
SUPPORT SYSTEM, I.E. BAR JOIST,
CONCRETE SLAB OR TIMBER FRAMING.
BOTTOM FLANGE AGAINST | CEILING |
UNDERSIDE OF TEES | TEE |
| BOTTOM VIEW OF |
| UNIT WITHOUT |
| LID ASSEMBLY |
1. | Disconnect power to air cleaner. |
2. | Mount 4” x 4” outlet box at desired remote location. |
3. | Attach 3/4” extension ring to outlet box. |
4. | Run five conductor, |
| the remote switch location to the air cleaner. |
5. | Use three wire nuts to connect three |
| wires on the remote switch to three |
| from the air cleaner. (Red, Blue, Violet) |
6. | Use one wire nut to connect white |
| wire from the air cleaner to single |
| the power supply. (White) |
BLACK
M10892
Fig. 5. Fasten cabinet to a structural support.
IMPORTANT
Do not touch the pleated filter media. Handle only the filter frame to prevent damage to the filter media.
11.Remove CPZ™ sorbent modules (select models) from their packaging and install one module into each cavity.
12.For Series 1 only. Be sure the fastener tabs are facing downward and fasten them.
13.For Series 2 and 3 only. Be sure both catches are turned down and filter rests firmly on catches.
14.Install the prefilter in the air cleaner lid. Position the metal screen mesh so it is facing upward when the lid is closed.
Remote 3 Speed Wall Switch (3 Speed Models only)
The 190097C Remote Wall Switch Assembly allows control of the F111 model air cleaners from a a location separate from the air cleaner. The assembly includes a remote switch with an outlet box cover, outlet box, extension ring, and a wire harness. Wiring to connect the remote switch and air cleaner must be furnished separately.
A100001
Fig. 6. Wiring 3-Speed Remote Switch
7.Connect the ground wire from the power supply to a ground stud of the outlet box.(Green)
8.Connect the ground wire from the air cleaner to the ground stud of the outlet box.(Green)
9.Use one wire nut to connect the black
10.Fold wires into box and mount remote switch on outlet box. Leave switch in OFF position.
11.On the air cleaner remove two screws on wiring com- partment cover and open
12.Run five conductor, color coded, 18 gauge wires from the remote switch through the air cleaner access open- ing into the wiring compartment. Strip ends of remote switch lead wires
13.Connect three wires on air cleaner to remote switch lead wires with wire nuts following color code used at remote switch. (Red, Blue, Violet)
6 |