Honeywell F111 Series 3 Make Opening if Mounting in a Drop Ceiling, Electrical Hookup

Models: F111 Series 3

1 12
Download 12 pages 40.69 Kb
Page 5
Image 5
Make Opening (if Mounting in a Drop Ceiling)

F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

latches (2)

3-speed switch module ( 3 Series only)

Make Opening (if Mounting in a Drop Ceiling)

1.Size the opening to fit the air cleaner cabinet as closely as possible.

2.Frame the opening to provide adequate support for the cabinet. The cabinet must fit snugly in the opening; allow no more than 1/4 in. (6 mm) from the opening to each side of the cabinet.

3.Cover the framing and any unused portion of the open- ing with wallboard, plywood, or other material and finish to match the ceiling.

Electrical Hookup

All wiring must comply with applicable codes and ordinances. The power source must agree with the model type: 120V, 60 Hz or 230V, 50 Hz.

1.Locate the prepunched hole in the side of the cabinet.

2.Remove the air cleaner lid.

3.For Series 1 and 2 only.Remove the connection box cover plate in the center cavity of the air cleaner.

4.For Series 3 only. Remove the connection box cover plate on the bottom, underneath the tray.

5.Refer to Fig. 3 and 4 for typical electrical diagrams.

Electrical Hookup WARNING

Risk of Fire or Electric Shock.

Can cause personal injury or equipment damage. Use only Honeywell 190097C Remote Speed Switch (3-speed models only) to regulate air cleaner speed. Using a different speed switch may void the warranty.

IMPORTANT

Be sure the air cleaner is grounded for correct operation and safety.

Canadian installation: NEVER install in ceilings with thermal insulation value greater than R-40.

 

 

 

 

 

 

 

 

 

 

 

FACTORY WIRING

 

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXTERNAL

CAPACITOR

 

BROWN

 

 

 

WIRING BY

 

 

 

 

 

MOTOR

INSTALLER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHITE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GREEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M12657

Fig. 3. Typical F111 (series 1 & 2) 120V, 60 Hz or

208/230V, 50/60 Hz wiring diagram.

 

 

 

 

 

 

 

 

 

FACTORY WIRING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

BLACK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REMOTE3-SPEED

SWITCH

EXTERNAL

CAPACITOR

 

BROWN

 

 

 

RED

 

 

 

 

 

 

MOTOR

 

BLUE

 

 

WIRING BY

 

 

 

 

 

 

 

 

 

INSTALLER

 

 

 

 

 

 

 

 

 

VIOLET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHITE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GREEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A100002

Fig. 4. Typical F111 Series 3 only 120V, 60 Hz or

230V, 50 Hz wiring diagram.

Mount Air Cleaner Cabinet

The air cleaner can be mounted in a drop ceiling system or hung in an open area. Both mounting methods require the air cleaner to be level and positioned facing downward for correct operation.

1.Remove the door/grille from the carton and set it aside.

2.Remove all filters.

3.Fit the cabinet into the prepared ceiling opening or position on the ceiling.

4.Use the four 3/8 x 16T internal nuts (one at each corner) to fasten the cabinet to a structural support (bar joist, concrete slab or timber framing). See Fig. 5.

NOTES:

All external hardware is furnished by the installer.

When using the suspension system of mounting, be sure to include a means for leveling adjust- ment after installation.

Never rest the air cleaner on the T-bar.

5.Level the air cleaner.

6.Turn the air cleaner power on and check for proper operation for 2 to 3 minutes. There should be a smooth, powerful blower sound and air discharging from both ends of the air cleaner.

7.Turn off the power.

8.Install the particle filter. Note airflow direction arrows if present. Install the filter with the direction arrow pointing towards the motor.

9.For Series 1 and 2 only. Fasten the filter tabs. Be sure there is a snapping sound when fastened. The tabs are commercial Velcro and require more force than lightly pushing them together.

10.For Series 3 only. Lock and secure the particle filter into place by closing both latches.