Honeywell Appendix B, Condition, Cause, Action Required, HE420A STEAM POWER HUMIDIFIER

Models: HE420A

1 8
Download 8 pages 54.14 Kb
Page 8
Image 8
APPENDIX B

HE420A STEAM POWER HUMIDIFIER

APPENDIX B

Table 4. Safety Control Relay (SCR) Operation and Troubleshooting Guide.

Condition

Cause

Action Required

 

 

 

SCR LED shows rapid series of red,

Condition Normal. SCR processor is

No action required.

green, and yellow lights, followed by

powering up and checking internal

 

no LED display.

operation.

 

Humidifier won't operate. No SCR

Problem! SCR circuit is not closing or

Check SCR power; check humidistat

LED display.

humidistat is not calling for humidity.

operation. If humidity is about 45% or

 

 

outdoor temperature is above 50°F,

 

 

the humidifier won't operate unless the

 

 

humidistat is set to Test mode.

Humidifier operates. SCR LED shows

Condition Normal. This is a test phase.

No action required.

continuous yellow.

SCR will wait 30 minutes to detect

 

 

furnace blower operation. If the

 

 

furnace blower is detected, the system

 

 

will function properly.

 

Humidifier won't operate. SCR LED

Problem! During the 30 minute test

Turn the humidistat off, then on again,

shows continuous red.

phase, the SCR failed to detect the

to reset the system. Although unlikely

 

furnace blower and turned the

to occur, this failure/reset process can

 

humidifier off.

occur twice before further action is

 

 

necessary.

Humidifier operates. SCR LED shows

Condition Normal. All systems

No action required.

continuous green.

(furnace, humidistat, humidifier and

 

 

SCR) are operating properly.

 

Humidifier won't operate. SCR LED

Problem! The SCR failed to detect the

Contact your HVAC contractor ASAP

shows flashing red.

furnace blower for the third time and,

to check out and repair the system.*

 

as a safety precaution, has locked out

 

 

the humidifier. This is an indication

 

 

that some aspect of the system

 

 

(furnace, humidistat, humidifier or

 

 

SCR) has malfunctioned.

 

*Before the SCR can be reset, the system must be checked and repaired by a licensed contractor. To reset the SCR, insert a rigid, small-diameter object (e.g. paperclip) into the smallest hole in the face of the SCR, next to the green connector block. This, too, should be performed by an HVAC contractor.

Automation and Control Solutions

 

 

 

Honeywell International Inc.

Honeywell Limited-Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, MN 55422

Scarborough, Ontario M1V 4Z9

customer.honeywell.com

 

 

 

® U.S. Registered Trademark

 

 

 

© 2006 Honeywell International Inc.

 

 

 

 

 

 

69-1108—2 M.S. Rev. 04-06

 

 

 

 

 

 

Page 8
Image 8
Honeywell installation instructions Appendix B, Condition, Cause, Action Required, HE420A STEAM POWER HUMIDIFIER