Motion Detector Walk Test
IMPORTANT:BeforecommencingwalktestensuretheLEDindicatorbehindthe
detector lens is not flashing continuously. If it is wait until the detector has completed
its warm-up cycle and the flashing stops.
Configurethedetectorforwalktestingaccordingtotheselected DayorNightoperat-
ing mode as follows:
1)Set theTIMEcontrolfullycounter-clockwisetoitsminimumsetting.
2)If thedetectorissettoDAYoperation(forusewith achime),adjusttheDUSK
control fully counter-clockwise to its minimum setting. If the detector is set to
NIGHToperation(forusewithlighting)adjustthe DUSKcontrolfullyclockwiseto
its maximum setting.
M27297
TIME
CONTROL
DUSK CONTROL
SETTING FOR
DAY OPERATION
DUSK CONTROL
SETTING FOR
NIGHT OPERATION
Fig. 5