T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS

 

 

Table 5. Installer System Test Options.

Keys to

Test

Description

Press

Number

Heating Equipment System-Test

Time

10

Enter heating equipment System Test.

!

11

Stage-one heat comes on. The system fan is also energized.

 

 

 

!

12

Stage-two heat comes on. Stage-one heat and system fan remain on.

 

 

 

"

11

Stage-two heat turns off.

 

 

 

"

10

Stage-one heat and system fan turn off.

 

 

 

Emergency

Heating Equipment System Test

Time

20

Change from heating to emergency heating equipment System Test.

!

21

Emergency heat come on.

 

 

 

"

20

Emergency heat turn off.

 

 

 

Cooling Equipment System Test

Time

30

Change from heating or emergency heating to cooling equipment System Test.

!

31

Cool and system fan come on.

 

 

 

"

30

Cool and system fan turn off.

 

 

 

Fan Equipment

System-

Test

Time

40

Change from cooling to fan equipment System Test.

!

41

Fan comes on.

 

 

 

"

40

Fan turns off.

 

 

 

Key Operation

System-Test

Time

60

Change from fan to key operation System Test.

NOTE: Press any key and the displayed numbers will change. Press Time to go to the previous test and Time to go to the next test. The Run Program key will not exit this test. Press Time or Time and then the Run Program key to exit.

69-1406—1