Installer setup
SettingFunctionPress DONE to exit & save settings.Press st to select functionPress st to change settingSetup functions Settings & Options (f actory default in bold)
0120 Year
(rst two digits)
20 (2000-2078)
21 (2101-2178)
0130 Year
(second two digits)
10 (2010)
[Other options : 00-99]
0140 Month 6 [Other optio ns: 1-12]
0150 Date 15 [Other options: 1-31]
0160 Schedule format 0 Nonprogrammable
4 Programmable
0165 Restore Ener gy
Saving Schedule
0 No
1 Yes
0170 System type 1 1 h eat/1 cool convent ional
2 1 h eat/1 cool heat pump (no au x. heat)
3 H eat only (2-wire systems)
4 H eat only with fan
5 H ot water Series 20 system (power to op en & close zone
valves/normally op en zone valves)
6 C ool only
7 2 h eat/1 cool heat pump (with au x. heat)
8 2 h eat/2 cool multistage c onventional
9 2 h eat/1 cool multistage conve ntional
10 1 heat/2 cool multist age conventional
11 2 heat/2 cool heat pum p (no aux. heat)
12 3 heat/2 cool heat pum p (with aux. heat)
0180 Fan control
(heating)
0 Gas/Oil heat (equipment controls heating fan)
1 Electric furnace (thermostat controls heating fan)
0190 Changeover valve
(O/B terminal)
0 O t erminal contro ls valve in cooling
1 B te rminal controls valve in heatin g
0220 1st stage compres-
sor cycle rate
3 Recommended for most compressors
[O ther options: 1, 2, 4 , 5 or 6 CPH]
0230 2nd stage compres-
sor cycle rate
3 R ecommended for most comp ressors
[O ther options: 1, 2, 4 , 5 or 6 CPH]
0240 1st stage heat
cycle rate (CPH =
cycles per hour)
5 G as or oil furnaces of l ess than 90% eff iciency
1 S team or gravity systems
3 H ot water systems & furnaces of 90 %+ efficiency
9 Electric furnaces
[ Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
Continued on next page