Setup functions Settings & Options (f actory default in bold)
0530 Adaptive Intelli-
gent Recovery™
1 On
0 Off
0540 Program periods 4 4 program perio ds (Wake, Leave, Retur n, Sleep)
2 2programperiods(Wake,Sleep)
0580 Compressor
protection
5 5 minute compre ssor off time
[Other options : 0, 1, 2, 3 or 4-minute off time]
0600 Heat temperature
range stop
90 Max. heat tempe rature settin g is 90°F (32°C)
[ Other options: 40- 89°F (4°C to 32°C)]
0610 Cool temperature
range stop
50 Min. cool temper ature setting i s 50°F (10°C)
[ Other options: 51-99°F (11°C to 37°C)]
0615 Energy Saving
Heat Setpoint
65 65°F (18.5°C)
4 0-90°F (4.5°C to 32°C)
0616 Energy Saving
Cooling Setpoint
78 78°F (25.5°C)
5 0-99°F (10°C to 37°C)
0640 Clock format 12 12-hour time (i.e., “ 3:30 pm”)
24 24-hour time (i.e., “15:30”)
0650 Extended fan
timer (heat)
0 Off
90 Fan runs for 90 seconds af ter call for heat ends
[Other options: 30, 6 0, 120]
0660 Extended fan
timer (cool)
0 Off
90 Fan runs for 90 seconds af ter call for cooling ends
[Other options: 30, 6 0, 120]
0670 Keypad lock 0 Keypad unlocked (fully functional)
1 Pa rtially locked (acce ss to temperature settings on ly)
2 Ful ly locked
0680 Heat temperature
control
2 Standard temperature control (recommended)
1 C hoose if room is warmer than set te mperature
3 C hoose if room does not reach set te mperature
0690 Cool temperature
control
2 Standard temperature control (recommended)
1 C hoose if room is cooler than se t temperature
3 C hoose if room does not reach set te mperature
0700 Temperature
display offset
0 T hermostat displays actua l room temperature
[ Other options: -3, -2, -1, 1, 2, 3°F offset (-1.5°C to 1.5°C)]
0710 Reset 0 No reset
1 Resetinstallero ptions(includingZ-Waveincl usion)&program
schedule to factory def ault (only date and time setti ngs are
retained)
rf10 Z-Wave Network
Connection
0 Remove
1 Add
rf20 Z-Wave Node
Connection
0 Idle
1 S end Node
Installer setup