Prestige™ Installation Guide

System-specific wiring guides

Heat pump systems

1H/1C Heat Pump [8]

C24VAC common

R Power [1]

Rc [R+Rc joined by jumper] O/B Changeover valve [7]

Y Compressor contactor **

G Fan relay **

2H/1C Heat Pump [9]

See [notes] below.

2H/2C Heat Pump [10]

C24VAC common

R Power [1]

Rc [R+Rc joined by jumper] O/B Changeover valve [7]

Y Compressor contactor (stage 1) ** Y2 Compressor contactor (stage 2)

G Fan relay **

C24VAC common

R Power [1]

Rc [R+Rc joined by jumper] O/B Changeover valve [7] Aux Auxiliary heat relay

Y Compressor contactor **

G Fan relay **

L Relay [12]

3H/2C Heat Pump [11]

C24VAC common

R Power [1]

Rc [R+Rc joined by jumper] O/B Changeover valve [7] Aux Auxiliary heat relay

Y Compressor contactor (stage 1) ** Y2 Compressor contactor (stage 2)

G Fan relay **

L Relay [12]

**[See note on page 4]

[1]

Power supply. Provide disconnect means and overload protection as required.

[2]

Remove jumper (R to Rc) for systems with two transformers. Common connection

 

must come from cooling transformer.

[3]

In Installer Setup, set

system type to Heat Only, No Fan.

[4]

In Installer Setup, set

system type to Conventional with zero cooling stages.

[5]

In Installer Setup, set

system type to Conventional with zero heat stages.

[6]

In Installer Setup, set

system type to Conventional with 2 heat AND 2 cool stages.

[7]

In Installer Setup, set changeover valve to O or B.

[8]

In Installer Setup, set to Heat Pump with 1 compressor stage and no auxiliary heat stages.

[9]

In Installer Setup, set to Heat Pump with 1 compressor stage and 1 auxiliary heat stage.

[10] In Installer Setup, set to Heat Pump with 2 compressor stages and no auxiliary heat stages.

[11] In Installer Setup, set to Heat Pump with 2 compressor stages and 1 auxiliary heat stage.

[12] “L” terminal sends a continuous output when thermostat is set to Em. Heat, and acts as a system monitor when in Heat, Cool or Off modes.

6