System-specific wiring guides

Humidification systems

Steam humidifier (or any humidifier with its own transformer) [3, 4]

Rc Power [1]

R[R+Rc joined by jumper] [2] HUM1 Humidifier relay [5] HUM2 Humidifier relay [5]

Dehumidification systems

Whole house dehumidifier [6]

Rc Power [1]

R[R+Rc joined by jumper] [2] DHM1Dehumidifier relay [5] DHM2Dehumidifier relay [5]

See [notes] below.

Bypass, flow-through humidifier (or any humidifier that uses the system transformer) [3]

Rc Power [1]

R[R+Rc joined by jumper] [2] HUM1 Field jumper R to HUM 1 [5] HUM2 Humidifier relay [5]

See [notes] below.

A/C with low-speed fan [7]

Rc Power [1]

R[R+Rc joined by jumper] [2] DHM1Field jumper Rc to DHM 1 [8] DHM2Dehumidifier relay [8, 9]

[1]

Power supply. Provide disconnect means and overload protection as required.

[2]

Remove jumper (R to Rc) for systems with two transformers. Common connection

 

must come from cooling transformer.

[3]

If using a humidifier that is wired directly to the thermostat, set humidification control

 

to Wired in Installer Setup.

[4]

If using a wireless adapter (THM4000R) with a TrueSTEAM humidifier, set humidification

 

control to Wireless in Installer Setup. Connect nothing to thermostat HUM terminals.

[5]

Terminals are normally open dry contacts.

[6]

In Installer Setup, set

dehumidification setting to Whole House Dehumidifier.

[7]

In Installer Setup, set

dehumidification setting to Dehumidify with Air Conditioner.

[8]

Terminals are normally closed dry contacts.

[9]

Equipment must include dehumidification terminal for low-speed fan.

7