Instructions for installation
The following instructions should be read by a qualified technician to ensure that the appliance is installed, regu- lated and technically serviced correctly in compliance with current regulations.
Important: remember to unplug the appliance from the mains before regulating the appliance or carrying out any maintenance work.
Positioning
Important: this appliance may be installed and used only in permanently ventilated rooms in compliance with cur- rent Norms in force. The following requirements must be observed.
a)The room must be equipped with an exhaust system that vents the combustion fumes to the outside. It may consist of a hood or an electric fan that automatically starts each time the appliance is turned on.
c)Intensive and prolonged use of the appliance may re- sult in the need for supplemental air circulation, e.g. opening windows or increasing mechanical venting (if present).
d)Liquid petroleum gas descends towards the floor as it is heavier than air. Thus, rooms containing LPG cylin- ders must also be equipped with apertures to the out- side for ventilation of gas in the event of leaks. LPG cylinders must not, therefore, be installed or stored in rooms or storage areas that are below ground level (cel- lars, etc.) whether they are partially or completely full. It is a good idea to keep only the cylinder being used in the room, positioned so that it is not subject to heat produced by external sources (ovens, fireplaces, stoves, etc. ) which could raise the temperature of the cylinder to above 50°C.
Prior to installing the cooker, 95 ÷ 155 mm high support- ing feet (provided) should be fitted into the holes to be found in the bottom of the cooker (fig.F). These feet are
In a chimney stack or branched flue | Directly to the outside |
(exclusively for cooking appliances) |
|
b)The room must also have a system to permit proper air circula- tion, needed for combustion to occur normally.The flow of air needed for combustion must not be less than 3 m3/h per kW of installed power.The air circulation system may take air directly from the outside by means of a pipe with an inner cross section of at least 100 cm2; the opening must not be able to be accidentally blocked. For those appliances not equipped with a safety device for accidental flame loss, the ventilation apertures must be in- creased by 100%, with the minimum being 200cm2 (Fig. A).The system can also provide the air needed for combustion by indi- rect means, i.e. from adjacent rooms fitted with air circulation tubes as described above.However, these rooms must not be
commonroomsorbedrooms.
|
| Detail A |
|
|
|
|
|
|
| Room | Room to be | ||||
|
|
|
|
|
|
|
|
|
|
|
| adjacent | ventilated | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A
Examples of ventilation holes | Enlarging the ventilation slot |
for comburant air | between |
Fig. A | window and floor |
| Fig. B |
min. 100mm
fig.F
fig.E | 155mm |
| 95÷ |
Installation of the cooker
The appliance can be installed next to furniture units which are no taller than the top of the cooker hob. The wall in direct contact with the back panel of the cooker must be made of
For
a)The appliance can be placed in a kitchen, dining room or bedsit, but not in a bathroom.
b)Any hoods must be installed according to the require- ments in the installation manual for the hoods them- selves.
c)If the cooker is installed beneath a wall cabinet, the latter must be situated at a minimum of 420 mm above the hob. The minimum distance between the worktop and kitchen units made of combustible material is 700 mm (Fig. C and D).
d)The wall in direct contact with the back panel of the cooker must be made of
3