Specifications
Power Specifications
Table 4-1: AC Input Requirements
| Nominal Value | Range |
Frequency (±5%) | 50 or 60 Hz | 47 to 63 Hz |
|
|
|
Voltage | 110 or 240 V | 90 to 254 V RMS |
|
| (autoranging) |
|
|
|
Steady state maximum current | At 240 V: 1.8 A (one power supply) or | — |
| 1.9 A (two power supplies) |
|
| At 120 V: 3.7 A (one power supply) or |
|
| 3.9 A (two power supplies) |
|
|
|
|
Standby current | 0.21 A at 240 V, 60 Hz | — |
| 0.15 A at 120 V, 60 Hz |
|
|
|
|
Environmental Specifications
Table 4-2: Environmental Specifications
| Operating | Shipping or Storage |
Ambient temperature | 10° to 35°C (5 0° to 95°F), with an aver age | |
| change of less than 1°C p er hour and a step | |
| change of less than 3°C p er hour | |
|
| |
|
|
|
Relative humidity | 40% to 60%, with a step change of less than | 10% to 80% |
(noncondensing) | 10% |
|
|
|
|
Air quality | Fewer than 500,000 particles 0.5 micron or | — |
| larger per cubic foot (approximately 17,700 per |
|
| liter) |
|
|
|
|
Heat dissipation | 1175 BTU/hr (345 W) | — |
|
|
|
HP StorageWorks Modular Smart Array 20 Maintenance and Service Guide |