INSTALLATION INSTRUCTIONS

 

 

 

 

3-phase R-22 Split System Heat Pump

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 16

 

 

 

 

 

 

R-22 Required Liquid Line

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature (°F) - Cooling Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rating Plate (required)

 

 

Rating Plate (required)

 

 

Measured Liquid

Subcooling Temperature (°F)

Measured Liquid

Subcooling Temperature (°F)

 

5

 

10

 

15

 

20

5

 

10

 

15

 

20

 

Pressure (psig)

 

 

 

Pressure (psig)

 

 

 

 

134

71

 

66

 

61

 

56

233

107

 

102

 

97

 

92

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

141

74

 

69

 

64

 

59

243

110

 

105

 

100

 

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

148

77

 

72

 

67

 

62

253

113

 

108

 

103

 

98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

156

80

 

75

 

70

 

65

264

116

 

111

 

106

 

101

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

163

83

 

78

 

73

 

68

274

119

 

114

 

109

 

104

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

171

86

 

81

 

76

 

71

285

122

 

117

 

112

 

107

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

179

89

 

84

 

79

 

74

297

125

 

120

 

115

 

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

187

92

 

87

 

82

 

77

309

128

 

123

 

118

 

113

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

196

95

 

90

 

85

 

80

321

131

 

126

 

121

 

116

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

205

98

 

93

 

88

 

83

331

134

 

129

 

124

 

119

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

214

101

 

96

 

91

 

86

346

137

 

132

 

127

 

122

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

223

104

 

99

 

94

 

89

359

140

 

135

 

130

 

125

 

SEQUENCE OF OPERATION

A. COOLING MODE

B. HEATING MODE

On a call for cooling, the thermostat makes circuits R-O, R-Y, and R-G. Circuit R-O energizes reversing valve, switching it to cooling position. Circuit R-Y energizes contactor, starting outdoor fan motor and compressor. Circuit R-G energizes indoor unit blower relay, starting indoor blower motor.

When thermostat is satisfied, its contacts open, de-energizing contactor and blower relay. Compressor and motors stop.

NOTE: If indoor unit is equipped with a time-delay relay circuit, the blower runs an additional length of time to increase system efficiency. (Applies to both cooling and heating modes.)

NOTE: Low ambient cooling feature allows unit to operate safely in cooling mode down to 0° F outdoor ambient.

On a call for heating, the thermostat makes circuits R-Y and R-G (circuit R-O is NOT made, and the reversing valve stays in the de-energized, heating position). Circuit R-Y energizes contactor, starting outdoor fan motor and compressor. Circuit R-G energizes indoor blower relay, starting blower motor. If the room temperature continues to fall, circuit R-W2 is made through the second-stage room thermostat bulb. Circuit R-W2 energizes a sequencer, bringing on the first bank supplemental electric heat and providing electrical potential to the second heater sequencer (if used). If outdoor temperature falls below the setting of the outdoor thermostat (field-installed option), contacts close to complete the circuit and bring on the second bank of supplemental electric heat.

When the thermostat is satisfied, its contacts open, de-energizing contactor, blower relay, and sequencer. Compressor, motors, and heaters stop.