INSTALLATION INSTRUCTIONS

3-phase R-22 Split System Heat Pump

 

 

 

 

 

 

 

 

 

Figure 19

 

Comfort Alertt Diagnostics (some models)

 

Miswired Module Indication

 

Troubleshooting Information

 

Green LED is not on, module

Determine if both R and C module terminals are connected. Verify voltage is

 

does not power up

present at module's R and C terminals.

 

 

 

 

Green LED intermittent, mod‐

Determine if R and Y terminals are wired in reverse. Verify module's R and C

 

ule powers up only when com‐

terminals have a constant source.

 

pressor runs

 

 

 

 

 

 

TRIP LED is on but system

Verify Y terminal is wired properly per OEM wiring diagram. Verify voltage at

 

and compressor check OK

contactor coil falls below 0.5VAC when off. Verify 24VAC is present across Y and

 

 

C when thermostat demand signal is present. If not, R and C are reverse wired.

 

 

 

 

TRIP LED and ALERT LED

Verify R and C terminals are supplied with 19-28VAC.

 

flashing together

 

 

 

 

 

 

ALERT Flash Code 3

Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at

 

(Compressor short cycling)

contactor coil falls below 0.5VAC when off.

 

displayed incorrectly

 

 

 

ALERT Flash Code 5 or 6

Check that compressor T1 and T3 wires are through module's current sensing

 

(Open Circuit, Missing Phase)

holes. Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at

 

displayed incorrectly

contactor coil falls below 0.5VAC when off.

 

 

 

 

ALERT Flash Code 8

Determine if module's Y terminal is connected. Verify Y terminal is connected to

 

(Welded Contactor) displayed

24VAC at contactor coil. Verify 24VAC is present across Y and C when

 

incorrectly

thermostat demand signal is present. If not, R and C are reversed wired. Verify

 

 

voltage at contactor coil falls below 0.5VAC when off. Review.

 

16

International Comfort Products, LLC

506 01 5001 00

Lewisburg, TN 37091