HP Performance Optimized Data Center (POD) 40cp manual High density HP POD

Models: Performance Optimized Data Center (POD) 40cp

1 21
Download 21 pages 18 Kb
Page 16
Image 16

High density HP POD

The high density HP POD must be supplied with six feeders.

3-phase

380 to 415V wye connected

50 to 60 Hz

225A

Each feeder must contain three phase conductors, one neutral conductor and one equipment ground conductor.

High density HP POD with redundant power

Component

Quantity

Phases

Amps

Volts

Description

 

 

 

 

 

 

Primary feeders

3

3

225

415/240

Supply primary power path to IT

 

 

 

 

 

equipment.

 

 

 

 

 

 

House power

2

3

100

415/240

One 100A feed to house panel A

feeders

 

 

 

 

to power convenience outlet,

 

 

 

 

 

lighting, and auxiliary equipment

 

 

 

 

 

provided with the HP POD.

 

 

 

 

 

The second 100A feed supplies

 

 

 

 

 

an alternate source of power to

 

 

 

 

 

house panel B if power path A

 

 

 

 

 

fails.

 

 

 

 

 

All house panel loads are supplied

 

 

 

 

 

from either house power panel A or B

 

 

 

 

 

through high speed contactors.

 

 

 

 

 

 

Redundant feeders

3

3

225

415/240

Supply secondary power path to IT

 

 

 

 

 

equipment.

 

 

 

 

 

 

Either the customer or HP (optional) supplies transformers to convert 3-phase, 480V delta power to 3- phase, 415V wye power, and switchboards to distribute branch circuit inputs to the HP POD.

NOTE: For locations outside North America, consult with HP regarding the requirements and specifications of transformers.

The customer must supply two 800A, 480V delta, 3-phase feeders to the transformers that will supply 415V 3 phase power to the HP POD. Each power source is capable of supporting the HP POD in the event of a power failure or planned maintenance.

Final connections to the HP POD can be supplied by the customer or by HP at additional cost.

High density HP POD without redundancy

Component

Quantity

Phases

Amps

Volts

Description

 

 

 

 

 

 

 

 

Primary feeders

3

3

225

415/240

Supply primary power path to IT

 

 

 

 

 

 

equipment.

 

 

 

 

 

 

 

 

House power

1

3

100

415/240

House panel A supplies power to HP

 

feeders

 

 

 

 

POD ECS, convenience outlet, lighting,

 

 

 

 

 

 

and auxiliary equipment provided with

 

 

 

 

 

 

Power management 16

Page 16
Image 16
HP Performance Optimized Data Center (POD) 40cp manual High density HP POD with redundant power