The HP POD ECS offers:
•The ability to monitor the status of water and air temperatures, water pressures, and water flow rates
•Immediate notification of supported alarm messages
For additional points that can be monitored, see the I/O (Input/Output) Controls Points List.
Fire, safety, and security notifications
Dry contacts are provided to enable the connection between the fire alarm system and the central facility fire detection system, relay alarm, and trouble conditions at each HP POD.
Your building fire, safety, and security system relays the following HP
Alarm | Meaning | Solution |
|
|
|
Smoke alarm | Smoke has been detected in the HP | Activate the EPO. Follow standard |
| POD. | emergency procedures for your |
|
| facility. |
|
|
|
Security | A security breach has occurred. | Follow standard emergency |
|
| procedures for your facility. |
|
|
|
EPO | Someone has activated the EPO | Follow standard emergency |
| system and shut down the HP POD. | procedures for your facility. |
|
|
|
The electrical layout of the fire alarm system is as described in the schematic drawing that is supplied with the HP POD.
Supported facility connections 20