Supported facility connections

Humidifier specifications

A dedicated supply of domestic water is required if the optional humidifier is installed. For specifications, see the humidifier manual supplied with the HP POD.

Item

Component

 

 

1

Humidifier drain and water supply

 

 

For more information about the humidifier, see the documentation developed by the humidifier manufacturer.

Convenience outlets

The HP POD is prewired for a convenience outlet on the inside of the unit. This circuit is not part of the power provided by the main switchboard feeding the 3 phase power to the HP POD. To energize this circuit, you must supply a dedicated single phase, 16-or 20-amp branch circuit from your facility at the appropriate voltage. Make sure that the branch circuit is connected to the prewired exterior mounted junction box and that it is wired in accordance with local regulations and codes.

Grounding requirements

The neutrals and equipment grounding conductors for all 3-phase HP POD feeders must remain isolated. The two conductors can be bonded at the power source only.

Functional and supplementary grounding straps are provided between each rack and HP POD.

IMPORTANT: Before installing the HP POD, consult your local AHJ for applicable codes and to review site-specific location guidelines. If needed, obtain any necessary permits.

Supported facility connections 18