UPS model

VA

Nominal power

Nominal voltage

 

 

rating (W)

setting

 

 

 

 

R1500 G3 INTL

1500

1000

220, 230, 240

Voltage specifications

Configuration setting (VAC)

Available nominal output voltage (VAC)

 

 

100

100

110

110

120

120

220

220

230

230

240

240

Output tolerance specifications

Source of power

Regulation

 

 

Utility power (nominal

-10% to +6% of nominal output voltage rating (within the

range)

guidelines of the Computer Business Equipment

 

Manufacturers Association)

 

 

Battery power

±20% of nominal output voltage rating

Output feature specifications

Feature

Specification

 

 

Online efficiency

95% nominal input voltage

Voltage wave shape

Sine wave; 5% THD with typical PFC load

Surge suppression

ANSI C62.41 Category A (formerly IEEE 587)

Noise filtering

Full-time EMI/RFI filtering

Battery specifications

Feature

Specification

 

 

Type

6 V, 9 AH, sealed, maintenance-free, valve-regulated,

 

rechargeable, lead-acid battery.

 

 

Voltage

The battery modules have a battery string voltage of 36 V.

Charging

Advanced charging for faster recovery. Complete charge takes at

 

least 48 hours. After approximately 24 hours, the batteries reach

 

90% charge at default nominal utility voltage and no load.

 

 

IMPORTANT: The 48-hour timer for the overall charge cycle triggers at the transition from charge mode to float mode. For certain conditions such as heavily discharged batteries, battery condition, and so on, it may take longer than usual to reach float mode. In these cases, it may take longer than 48 hours to reach the rest mode.

Specifications 35