UPS model | VA | Nominal power | Nominal voltage |
|
| rating (W) | setting |
|
|
|
|
R1500 G3 INTL | 1500 | 1000 | 220, 230, 240 |
Voltage specifications
Configuration setting (VAC) | Available nominal output voltage (VAC) |
|
|
100 | 100 |
110 | 110 |
120 | 120 |
220 | 220 |
230 | 230 |
240 | 240 |
Output tolerance specifications
Source of power | Regulation |
|
|
Utility power (nominal | |
range) | guidelines of the Computer Business Equipment |
| Manufacturers Association) |
|
|
Battery power | ±20% of nominal output voltage rating |
Output feature specifications
Feature | Specification |
|
|
Online efficiency | 95% nominal input voltage |
Voltage wave shape | Sine wave; 5% THD with typical PFC load |
Surge suppression | ANSI C62.41 Category A (formerly IEEE 587) |
Noise filtering |
Battery specifications
Feature | Specification |
|
|
Type | 6 V, 9 AH, sealed, |
| rechargeable, |
|
|
Voltage | The battery modules have a battery string voltage of 36 V. |
Charging | Advanced charging for faster recovery. Complete charge takes at |
| least 48 hours. After approximately 24 hours, the batteries reach |
| 90% charge at default nominal utility voltage and no load. |
|
|
IMPORTANT: The
Specifications 35