Battery runtime

Load, percent

Load, watts

Estimated battery runtime at 100% battery charge

 

 

 

20

200

58 minutes

50

500

17 minutes

80

800

8 minutes

100

1000

5 minutes

Environmental specifications

Feature

Specification

 

 

Operating temperature

0°C to 35°C (32°F to 95°F)

Nonoperating temperature

-15°C to 55°C (5°F to 131°F)

Relative humidity

5% to 95%; noncondensing

Operating altitude

Up to 3,000 m (9,843 ft) above sea level

Nonoperating altitude

Up to 15,000 m (49,212 ft) above sea level

Audible noise

Less than 45 dBA

Serial communications port pin assignment

Pin number

Signal name

Function

Direction from the UPS

 

 

 

 

1

Low batt

Low battery relay contact; 20 mA, 30 Vdc contact

Out

 

 

rating

 

2

TxD

Transmit to external device

Out

 

 

 

 

3

RxD

Receive from external device

In

 

 

 

 

4

DTR

PnP from external device (tied to Pin 6)

In

 

 

 

 

Specifications 36