hussman Q1-DC operation manual Refrigeration Contd, Electrical

Models: Q1-DC

1 35
Download 35 pages 36.96 Kb
Page 6
Image 6

Q1-DC-0508

Refrigeration (Cont'd)

Electronic Expansion Valve (Optional)

A wide variety of electronic expansion valves and case controllers can be utilized. Please refer to EEV and controller Hussmann’s information sheet. Sensors for electronic expansion valves will be installed on the coil inlet, coil outlet, and in the discharge air. (Some supermarkets require a 4th sensor in the return air). Case controllers will be located in the electrical raceway or under the case.

Expansion Valve Adjustment

Expansion valves must be adjusted to fully feed the evaporator. Before attempting any adjustments, make sure the evaporator is either clear or very lightly covered with frost, and that the fixture is within 10°F of its expected operating temperature.

After case has been brought to running temperature

verify screws along glass clamp aluminum

extrusion are tight.

Measuring the Operating Superheat

1.Determine the suction pressure with an accurate pressure gauge at the evaporator outlet.

2.From a refrigerant pressure temperature chart, determine the saturation temperature at the observed suction pressure.

3.Measure the temperature of the suction gas at the thermostatic remote bulb location.

4.Subtract the saturation temperature obtained in step No. 2 from the temperature measured in step No. 3.

5.The difference is superheat.

6.Set the superheat for 5°F - 7°F.

Thermostat Location

Thermostats are located in the electrical section; behind the rear panel, on the right-hand side of the case (facing the back of the case).

Wiring Color Code

Electrical

 

The receptacle that is provided on the exterior back of these

 

models is intended for computerized scales with a five amp

 

maximum load, not for large motors or other high wattage

 

appliances. It should be wired to a dedicated circuit.

 

 

 

 

 

 

 

 

 

 

BEFORE SERVICING

ALWAYS DISCONNECT ELECTRICAL

POWER AT THE MAIN DISCONNECT

WHEN SERVICING OR REPLACING ANY

ELECTRICAL COMPONENT.

This includes (but not limited to) Fans, Heaters

Thermostats, and Lights.

CASE MUST BE GROUNDED

NOTE: Refer to label affixed to case to determine the actual configuration as checked in the “TYPE INSTALLED” boxes.

Electrical Circuit Identification

Standard lighting for all models will be full length fluorescent lamps located within the case at the top. The switch controlling the lights, the plug provided for digital scale, and the thermometer are located at the rear of the case mullion.

Field Wiring and Serial Plate Amperage

Field Wiring must be sized for component amperes printed on the serial plate. Actual ampere draw may be less than specified. Field wiring from the refrigeration control panel to the merchandisers is required for refrigeration thermostats. Case amperes are listed on the wiring diagram, but always check the serial plate.

Ballast Location

Ballasts are located within the access panel that runs the length of the rear of the case.

Page 6
Image 6
hussman Q1-DC operation manual Refrigeration Contd, Electrical