IGFP-R3, R3P-0608

Plumbing

Waste Outlet and P-TRAP

The waste outlet is located off the center of the case on one side allowing drip piping to be run lengthwise under the fixture. There are 3 drains in each fixture that can be easily located.

1-1/2", 1" and 3/4" P-TRAPS and threaded adapters are supplied with each fixture. The 3 P-TRAPS must be installed to prevent air leakage and insect entrance into the fixture.

NOTE: PVC-DWV solvent cement is recommended. Follow the manufacturer’s instructions.

Installing Condensate Drain

Poorly or improperly installed condensate drains can seriously interfere with the operation of this refrigerator, and result in costly maintenance and product losses. Please follow the recommendations listed below when installing condensate drains to insure a proper installation:

1.Never use pipe for condensate drains smaller than the nominal diameter of the pipe or P-TRAP supplied with the case.

2.When connecting condensate drains, the P-TRAP must be used as part of the condensate drain

to prevent air leakage or insect entrance. Store plumbing system floor drains should be at least 14" off the center of the case to allow use of the P-TRAP pipe section. Never use two water seals in series in any one line. Double P-TRAPS in series will cause a lock and prevent draining.

3.Always provide as much down hill slope ("fall") as possible; 1/8" per foot is the preferred minimum. PVC pipe, when used, must be supported to maintain the 1/8" pitch and to prevent warping.

4.Avoid long runs of condensate drains. Long runs make it impossible to provide the "fall" necessary for good drainage.

5.Provide a suitable air break between the flood rim of the floor drain and outlet of condensate drain. 1" is ideal.

6.Prevent condensate drains from freezing:

a.Do not install condensate drains in contact with non-insulated suction lines. Suction lines should be insulated with a non - absorbent insulation material such as Armstrong's Armaflex.

b.Where condensate drains are located in dead air spaces (between refrigerators or between a refrigerator and a wall), provide means to prevent freezing. The water seal should be insulated to prevent condensation.

Refrigeration

Refrigerant Type

The standard refrigerant will be R-22 unless otherwise specified on the customer order. Check the serial plate on the case for information.

Piping

The refrigerant line outlets are located under the case.

Locate first the electrical box, the outlets are then on the

same side of the case but at the opposite end. Insulate suction lines to prevent condensation drippage.

Refrigeration Lines

 

Liquid

Suction

3/8” O.D.

5/8” O.D.

NOTE: The standard coil is piped at 5/8” (suction); however, the store tie-in may vary depending on the number of coils and the draw the case has. Depending on the case setup, the connecting point in the store may be 5/8”, 7/8”, or 11/8”. Refer to the particular case you are hooking up.

Refrigerant lines should be sized as shown on the refrigeration legend furnished by the store.

Install P-TRAPS(oil traps) at the base of all suction line vertical risers.

Pressure drop can rob the system of capacity. To keep the pressure drop to a minimum, keep refrigerant line run as short as possible, using the minimum number of elbows. Where elbows are required, use long radius elbows only.

Control Settings

See R3, R3P technical data sheet for the appropriate settings for your merchandiser. Maintain these parameters to achieve near constant product temperatures. Product temperature should be measured first thing in the morning, after having been refrigerated overnight. Defrost times should be as follows: OFF CYCLE - Defrost times should be as directed in the R3, R3P technical data sheet. The number of defrosts per day and the duration of the defrost cycle may be adjusted to meet conditions present at your location.

Access to TX Valves and Drain Lines

Mechanical - Remove product from end of case. Remove product racks. Remove refrigeration and drain access panels (labeled). TX valve (mechanical only) and drain are located under each access panel at end of the case.

Electronic - The Electronic Expansion valve master and slave cylinder(s) are located within the electrical access panel(s).

12

Page 12
Image 12
hussman R3P-0608, IGFP-R3, Refrigerated Service and/or Prep with Refrigerated Self Service Front Plumbing, Refrigeration

IGFP-R3, R3, R3P, R3P-0608, Refrigerated Service and/or Prep with Refrigerated Self Service Front specifications

Hussmann Refrigerated Service and Prep Solutions offer innovative designs and advanced technologies that cater to the dynamic needs of the modern retail environment. Among their impressive line-up, the Refrigerated Self-Service Front models, particularly the R3P-0608 and its variants, stand out for their effective combination of functionality, energy efficiency, and user-friendly features.

The R3P series exemplifies Hussmann's commitment to providing high-quality refrigeration solutions that enhance customer experience. With a sleek design, these service fronts are not only appealing but also practical for various food service applications, including convenience stores and grocery operations. The self-service model allows customers easy access to a wide range of products, ensuring a seamless shopping experience whether it’s for pre-packaged meals, salads, or beverages.

One of the main features of the R3P series is its energy-efficient technology. Equipped with advanced refrigeration systems, these models operate effectively while maintaining optimal food temperatures. Hussmann integrates Eco-Design principles into the R3P, which help reduce its overall energy consumption without compromising performance. This is vital in today's retail environment, where operational costs continue to rise, and sustainability is a key customer concern.

The innovative design of the R3P also includes adjustable shelving and customizable display options, enabling retailers to optimize space for various product types. This flexibility allows businesses to display items clearly and attractively while maximizing visual appeal and accessibility. Additionally, the ergonomic design of the glass doors ensures easy access for both customers and staff, streamlining operations and improving product visibility.

The IGFP-R3 variant further exemplifies Hussmann's advanced technology with integrated features such as smart temperature controls and monitoring systems. This variant is designed to enhance food safety by ensuring that products are kept at the recommended temperatures, providing peace of mind to both retailers and consumers.

Overall, Hussmann Refrigerated Service and Prep solutions, particularly the R3P-0608 and related models, represent an ideal blend of style, efficiency, and functionality. The emphasis on energy savings, customization, and food safety makes these solutions integral to the success of modern food retail and service environments. As retailers continue to seek competitive edges, the R3P series by Hussmann remains a leading choice in refrigeration technology, offering exceptional value and innovation.