IBM IBM UPS 7500XHV, IBM UPS 10000XHV setup guide Emergency Power Off EPO Option, EPO Switch

Models: IBM UPS 7500XHV IBM UPS 10000XHV

1 29
Download 29 pages 38.85 Kb
Page 19
Image 19
Emergency Power Off (EPO) Option

NOTE: SETTINGS ARE MADE THROUGH THE SUPPLIED POWERCHUTE BUSINESS EDITION SOFTWARE, NETWORK MANAGEMENT CARD, OR TERMINAL MODE. REFER TO THE SOFTWARE HELP GUIDES FOR DETAILS.

 

FUNCTION

 

FACTORY

USER SELECTABLE

 

DESCRIPTION

 

 

 

DEFAULT

 

CHOICES

 

 

 

 

 

 

 

 

 

 

Output Frequency

Automatic

Automatic,

 

The user is able to set the allowable

 

 

 

(50 ± 3 Hz or

50

± 3 Hz,

 

uninterruptible power supply output

 

 

 

50

± 0.1 Hz,

 

frequency. Whenever possible, the

 

 

 

60 ± 3 Hz)

 

 

 

 

60

± 3 Hz,

 

output frequency tracks the input fre-

 

 

 

 

 

 

 

 

 

60

± 0.1 Hz

 

quency.

 

 

 

 

 

 

 

Number of Battery

1

Number of Con-

 

The user can define the number of con-

 

Packs

 

nected Battery Packs

 

nected battery packs for proper runtime

 

 

 

 

(four battery modules

 

prediction.

 

 

 

 

per pack)

 

 

 

 

 

 

 

 

 

 

 

 

Emergency Power Off (EPO) Option

The output power can be disabled in an emergency by closing a switch connected to the EPO.

Note: Adhere to national and local electrical codes when wiring.

The switch should be connected in a normally open switch contact. External voltage is not required; the switch is powered by a 12 V internal power supply. A closed switch draws 2 mA of current.

The EPO switch is internally powered by the uninterruptible power supply for use with non-powered switch circuit breakers. Note: The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and an SELV circuit (IEC standard).

EPO

Switch

Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV.

If the circuit standard cannot be confirmed, use a contact closure switch.

Use one of the following cable types to connect the uninterruptible power supply to the EPO switch:

CL2: Class 2 cable for general use

CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air

CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft

CLEX: Limited use cable for use in dwellings and for use in raceways

For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable)

For installation in other countries: Use a standard low-voltage cable according to local regulations