IBM SG24-5360-00 manual Range of Cylinders

Models: SG24-5360-00

1 84
Download 84 pages 35.07 Kb
Page 33
Image 33

4.1.2 A Range of Cylinders

You copy a range of cylinders by identifying the device address or VOL1 label of the source and target in the IXFP SNAP command. In addition, the decimal start cylinder (scyl) and end cylinder (-scyl) or number of cylinders (,ncyl) are specified in parentheses and appended to the source specification. Optionally, the target start cylinder (tcyl) can be included to specify where copying is to start on the target device.

To illustrate, we use two volumes: PATEV1 and PATEV2. The device addresses of these volumes are 80E and 80F, respectively. To copy cylinders 0 through 999 in the first volume onto the second volume, issue one of the following commands:

IXFP SNAP,80E(0000-0999):80F,NOPROMPT

IXFP SNAP,80E(0000,1000):80F,NOPROMPT

IXFP SNAP,PATEV1(0000-0999):PATEV2,NOPROMPT

IXFP SNAP,PATEV1(0000,1000):PATEV2,NOPROMPT

You specify the target start-cylinder (tcyl) to relocate the range of cylinders on the target volume. Indicate target start-cylinder 1000 to relocate the range of cylinders on the target volume. You can issue one of the following modified commands:

IXFP SNAP,80E(0000-0999):80F(1000),NOPROMPT

IXFP SNAP,80E(0000,1000):80F(1000),NOPROMPT

IXFP SNAP,PATEV1(0000-0999):PATEV2(1000),NOPROMPT

IXFP SNAP,PATEV1(0000,1000):PATEV2(1000),NOPROMPT

You may or may not include the NOPROMPT parameter to prevent or allow decision-type messages (see Figure 13 on page 22).

Notes:

If the source is identified by its VOLID, it must be either the only volume with that VOLID or the only VOLUME with that VOLID which is up (DVCUP). Otherwise an error message will be issued.

The target device must be down (DVCDN) before you initiate the volume snap, except when the source and the target device are the same device.

If the target device is identified by its VOLID, it must be either the only volume with that VOLID or the only volume with that VOLID which is down (DVCDN). Otherwise an error message will be issued.

The highest (end) cylinder number must not exceed 32767 or the maximum number of cylinders of the devices. The start cylinder number must not be greater than the end cylinder number.

You cannot use the VOL1 parameter when copying cylinder ranges.

Cylinder range copying is done unconditionally within the specified or assumed boundaries. VSE does not perform any VTOC checking on the specified target device and thus does not provide any warning messages regarding overlapping extents or secured or unexpired files.

Chapter 4. IXFP/SnapShot for VSE/ESA 23

Page 33
Image 33
IBM SG24-5360-00 manual Range of Cylinders