OPERATION

utility (preferred source)

generator (alternate source)

acceptable light

acceptable light

 

exerciser

 

light

transfer switch on utility

transfer switch on generator

(preferred source) light

(alternate source) light

INDICATOR LIGHTS

On the front control display are five lights that indicate the status of the sources and the automatic transfer switch.

Utility (preferred source) acceptable (light at the top left of the display)

When on, this light indicates that the utility voltage is acceptable for connection to the load.

Generator (alternate source) acceptable (light at the top right of the display)

When on, this light indicates that the generator voltage and frequency are acceptable for connection to the load.

Transfer Switch on utility (preferred source) (light at the center left of display)

When on, this light indicates that the load is connected to the utility (preferred source).

Transfer Switch on generator (alt. source) (light at the center right of display)

When on, this light indicates that the load is connected to the generator (alternate source).

Automatic Generator Exerciser

(light above button at the right of display)

When the utility is acceptable and the load is on the utility, this light flashes the number of days until the next exercise period. When it is off, no exerciser period is set. The light is also off any time the generator is running.

PUSH BUTTONS

On the front control display are two push buttons that control the operation of the generator and the automatic transfer switch.

Push to Test (button on the left side)

This button is used to test the system. See the Manual Generator Testing section on the next page.

This button can be used to cancel any active time delay. Press and release the button to bypass the time delay.

This button can be used to clear displayed error codes. See Troubleshooting section, Problem 8.

Automatic Generator Exerciser (right button)

This button is used to set the automatic generator exerciser. See the next page.

UTILITY FAILURE

The load is normally connected to the preferred source (utility) if that source is acceptable. If the preferred source

(utility) fails, the following sequence occurs:

1.The UTILITY source acceptable light goes off.

2.The automatic transfer switch waits three seconds to pre- vent nuisance starting of the generator from momentary dips of the utility voltage. If the utility is restored during the three seconds, the UTILITY source acceptable light comes on and no further action is taken.

3.If the utility remains unacceptable for three seconds, the automatic transfer switch cranks and starts the generator.

4.Once the generator starts, the automatic transfer switch waits until the generator voltage and frequency are acceptable. Then the GENERATOR source acceptable light comes on.

5.When the generator is acceptable, the automatic transfer switch waits 15 seconds to allow the generator to warm up. Then it transfers the load to the generator. The TRANSFER SWITCH on generator (alternate source) light comes on.

6.The automatic transfer switch waits for the utility source to be restored. When the utility again becomes acceptable the UTILITY source acceptable light comes on.

7.The automatic transfer switch then waits 5 minutes to allow the utility to stabilize. Then it retransfers the load back to the utility. The TRANSFER SWITCH on utility (preferred source) light comes on.

8.After load retransfer the generator will continue to run unloaded for one minute for engine cooldown. Then it is stopped. The GENERATOR acceptable light goes off.

6