![ECONOMIZER WITH SINGLE ENTHALPY SENSOR -](/images/new-backgrounds/35841/3584163x1.webp)
ECONOMIZER WITH SINGLE ENTHALPY SENSOR -
When the room thermostat calls for cooling, the low voltage control circuit from “R” to “G” and “Y1” is com- pleted. The UCB energizes the blower motor (if the fan switch on the room thermostat is set in the “AUTO” position) and drives the economizer dampers from fully closed to their minimum position. If the enthalpy of the outdoor air is below the setpoint of the enthalpy con- troller (previously determined), “Y1” energizes the economizer. The dampers will modulate to maintain a constant supply air temperature as monitored by the discharge air sensor. If the outdoor air enthalpy is above the setpoint, “Y1” energizes the compressor and condenser fan motor only.
Once the thermostat has been satisfied, it will
ECONOMIZER WITH DUAL ENTHALPY SENSORS -
The operation with the dual enthalpy sensors is identi- cal to the single sensor except that a second enthalpy sensor is mounted in the return air. This return air sen- sor allows the economizer to choose between outdoor air and return air, whichever has the lowest enthalpy value, to provide maximum operating efficiency.
ECONOMIZER (SINGLE OR DUAL) WITH POWER EXHAUST -
This system operates as specified above with one addition. The power exhaust motor is energized 45 seconds after the actuator position exceeds the exhaust fan setpoint on the economizer control. When the power exhaust is operating, the second stage of mechanical cooling will not operate. As always, the “R” to “G” connection provides minimum position but does not provide power exhaust operation.
MOTORIZED OUTDOOR AIR DAMPERS -
This system operation is the same as the units with no outdoor air options with one exception. When the “R” to “G” circuit is complete, the motorized damper drives
open to a position set by the thumbwheel on the damper motor. When the “R” to “G” circuit is opened, the damper spring returns fully closed.
COOLING OPERATION ERRORS
Each cooling system is monitored for operation outside of the intended parameters. Errors are handled as described below. All system errors override minimum run times for compressors.
HIGH-PRESSURE LIMIT SWITCH
During cooling operation, if a
Should a
LOW-PRESSURE LIMIT SWITCH
The
Once the
If the call for cooling is still present at the conclusion of the ASCD, the UCB will
Should a
FREEZESTAT
During cooling operation, if a freezestat opens, the UCB will
32 | Johnson Controls Unitary Products |