Keating Of Chicago Miraclean Thermostat Bulb Placement Detail, A. Burner Coil Check

Models: Miraclean

1 17
Download 17 pages 1.52 Kb
Page 13
Image 13
THERMOSTAT BULB PLACEMENT DETAIL

THERMOSTAT BULB PLACEMENT DETAIL

MILLIVOLT CHECK (FOR QUALIFIED SERVICE TECHNICIANS ONLY)

The millivolt valve is a thermopile self-powered combination gas control. Before checking the millivolt system, the following operations should be performed and observations made:

1.A genuine Keating millivolt thermostat should be used for millivolt operation.

2.The thermostat leads and all wire connections should be cleaned and tightened to eliminate all unnecessary resistance.

3.If pilot will not remain lit when gas valve knob is released, check automatic pilot.

NOTE: The millivolt system and individual components may be checked with a millivolt meter having a 1-1000MV range. Conduct each check below by connecting meter test leads to terminals as indicated. All readings are closed circuit.

 

 

CONNECT METER LEADS TO

THERMOSTAT

METER READING

CHECK

TO TEST

 

TERMINALS

CONTACTS

SHOULD BE:

 

 

 

 

 

 

A

BURNER COIL

TP

TH

CLOSED

100mV OR MORE

 

 

 

 

 

 

B

THERMOPILE OUTPUT

THTP

TP

OPEN

BETWEEN 325–700mV

 

 

 

 

 

 

C

THERMOSTAT LOAD

THTP

TH

CLOSED

DROPS LESS THAN 80mV

 

 

 

 

 

 

D

AUTOMATIC PILOT DROPOUT

THTP

TP

OPEN

BETWEEN 75-25 mV

 

 

 

 

 

 

A. BURNER COIL CHECK

(“A” Reading. Thermostat contacts CLOSED - Gas Valve knob “ON”. Main burner should come ON.)

1.If the reading is more than 100 millivolts and the automatic valve still does not come one, replace the valve.

2.If the closed circuit reading (“A” reading) is less than 100 millivolts, determine cause for low reading and proceed as follows:

11

Page 13
Image 13
Keating Of Chicago Miraclean installation manual Thermostat Bulb Placement Detail, A. Burner Coil Check