THERMOSTAT BULB PLACEMENT DETAIL
MILLIVOLT CHECK (FOR QUALIFIED SERVICE TECHNICIANS ONLY)
The millivolt valve is a thermopile
1.A genuine Keating millivolt thermostat should be used for millivolt operation.
2.The thermostat leads and all wire connections should be cleaned and tightened to eliminate all unnecessary resistance.
3.If pilot will not remain lit when gas valve knob is released, check automatic pilot.
NOTE: The millivolt system and individual components may be checked with a millivolt meter having a
|
| CONNECT METER LEADS TO | THERMOSTAT | METER READING | |
CHECK | TO TEST |
| TERMINALS | CONTACTS | SHOULD BE: |
|
|
|
|
|
|
A | BURNER COIL | TP | TH | CLOSED | 100mV OR MORE |
|
|
|
|
|
|
B | THERMOPILE OUTPUT | THTP | TP | OPEN | BETWEEN |
|
|
|
|
|
|
C | THERMOSTAT LOAD | THTP | TH | CLOSED | DROPS LESS THAN 80mV |
|
|
|
|
|
|
D | AUTOMATIC PILOT DROPOUT | THTP | TP | OPEN | BETWEEN |
|
|
|
|
|
|
A. BURNER COIL CHECK
(“A” Reading. Thermostat contacts CLOSED - Gas Valve knob “ON”. Main burner should come ON.)
1.If the reading is more than 100 millivolts and the automatic valve still does not come one, replace the valve.
2.If the closed circuit reading (“A” reading) is less than 100 millivolts, determine cause for low reading and proceed as follows:
11