Start Up Conditions
TNERMAL EXPANSmON
Property Damage Hazard
° Avoid water heater damage.
o Install thermal expansion tank or device if necessary. o Contact qualified installer or service agency.
Water supply systems may, because of such events as high line pressure, frequent
among others, have installed devices such as pressure
reducing valves, check valves, back flow preventers, etc._to control these types of problems. When these devices are not equipped with an internal
water is heated, it expands (thermal expansion) and closed systems do not allow for the expansion of heated water.
The water within the water heater tank expands as it is heated and increases the pressure of the water system. If the relieving
point of the water heater's
reached, the valve wil! relieve the excess pressure. The
temperatureopressure relief valve is not intended for the
constant relief of thermal expansion. This is an unacceptable condition and must be corrected.
It is recommended that any devices installed which could create a closed system have a
expansion tank to relieve the pressure built by thermal
expansion in the water system. Thermal expansion tanks are available from Sears stores and through the Sears Service Centers. Contact the local plumbing inspector, water supplier
and/or the Sears Service Center for assistance in controlling these situations.
Therma! Expansion | Tank | Specifications |
| |||
|
| Tank |
| Dimensions | Pipe | |
|
|
|
|
|
| |
Model |
| Capacity |
| in inches | Fitting | |
Number | in | Gallons | _m |
| Length | On Tank |
|
|
| ||||
153.331020 |
| 2 | 8 (203 | ram) | 3/4" Mate | |
153.331050 |
| 5 | 11 (279 | mm) | 3/4" Mate | |
|
|
|
| Expansion | Tank | Sizing | Chart |
|
|
| h[et* | Water | Heater | Capacity |
| (Gallons) |
| Water |
| E |
|
|
|
| Pressure |
|
|
|
| |
| 30 | 40 | 50 | 66 | 82 | |
Expansion | 40psi | 2 | 2 | 2 | 5 | 5 |
Tank | 50psi | 2 | 2 | 2 | 5 | 5 |
Capacity | 60psi | 2 | 2 | 5 | 5 | 5 |
Needed | 70psi | 2 | 2 | 5 | 5 | 5 |
| 80psi | 2 | 5 | 5 | 5 | 5 |
*Highest recorded inlet water pressure in a 24 hour period or regulated water pressure.
NOTE: Expansion tanks are preocharged with a 40 psi air
charge. Bfthe inlet water pressure is higher than 40 psi, the
expansion tank's air pressure must be adjusted to match
that pressure, but must not be higher than 80 psi.
WATER | HEATER | (3) |
COLD | WATER | PRESSURE |
0NLET FITTING | REDUCING |
VALVE WITH
{2)
PRESSURE GAUGE | ruNLET COLD | ||
|
| WATER | |
RECOMMENDED | mNSTALLATION |
| |
IVERTICAL | MOUNTING) |
| |
WATER HEATER |
|
|
|
COLD WATER |
|
|
|
INLET FITTING | FLOOR, | CEILING | JOIST, ETC. |
|
PRESSURE
REDUCING
_ STRAPPING(3)
_%"(1) VALVEWITHBY=PASS
EXPANSmON /
TANK
!2) | / | f |
PRESSUREGAUGE | #1LETCOLD |
WATER
ALTERNATE RECOMMENDED INSTALLATION
{HORIZONTAL MOUNTING)
FIGURE 43.
STRANGE SOUNDS
Possible noises due to expansion and contraction of some
metal parts during periods of
Operationa_ Conditions
SMELLY WATER
In each
rod (see parts section) for corrosion protection of the tank.
Certain water conditions will cause a reaction between this
rod and the water. The most common complaint associated with the anode rod is one of a "rotten egg smell'L This odor is derived from hydrogen sulfide gas dissolved in the wateE The smell is the result of four factors which must all be present for the odor to develop:
A A concentration of sulfate in the supply water.
B. Little or no dissolved oxygen in the water.
C. A sulfate reducing bacteria within the water heater. (This harmless bacteria is nomtoxic to humans.)
23