LookatthetopofthewaterheaterThecoldwaterinletis. marked"COLD"Puttwoorthreeturnsofteflontape.around
the threaded end of the
NOTE: This water heater is super insulated to minimize heat loss from the tank. Further reduction in heat loss can be accomplished by insulating the hot water lines from the water heater.
INSTALLATION COMPLETED USING
INSTALLATION KIT
FLEXIBLE
WATER
CONNECTORS
fit s=v :F
SWEAT COUPLI |
|
| WEAT COUPLING |
THREADED T!_G _ | r_ | _ | s THREADED TO |
DRAFT HOOD
TEMPERATURE -
PRESSURE
RELIEF VALVE
DISCHARGE PIPE
(Do not cap or plug)
%
AIR
GAP
FLQORDRAIN
FIGURE15.
Temperature-Pressure Relief Valve
| Explosion | Hazard |
| ||
| |||||
| must comply with ANSI Z21.22 | ||||
_J | and ASME | code, |
|
| |
| Properly | sized | temperature- | ||
| pressure relief valve must be | ||||
| installed in opening | provided. |
| ||
| Can result | in | overheating | and | |
| excessive | tank | pressure. |
|
Can cause serious injury or death.
This heater is provided with a properly certified combination temperature - pressure relief valve by the manufacturer.
The valve is certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief Valves and Automatic Gas
Supply Systems, ANSI Z21,22 and the code requirements of ASME,
if replaced, the valve must meet the requirements of local codes, but not less than a combination temperature and pressure relief valve certified as indicated in the above paragraph,
The valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 psi = 1,035kPa) and a discharge capacity not less than the water heater input rate as shown on the model rating plate.
For safe operation of the water heater, the relief valve must not be removed from its designated opening nor plugged,
The
under any circumstances. Excessive length, over 30 feet (9.14 m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve.
No valve or other obstruction is to be placed between the relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6 inch air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must
be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.
Water Damage Hazard
•Temperature_pressurerelief valve discharge pipe muetterminate at adequate drain•
The Discharge Pipe:
•Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions.
•Shall not be plugged or blocked.
•Shall be of material listed for hot water distribution.
•Shall be installed so as to allow complete drainage of both the
•Shall terminate at an adequate drain.
•Shall not have any valve between the relief valve and tank.
13