Code | Fault | Remedy |
14 | Thermal Fuse | Check gas type of unit and ensure it matches gas type being used. |
|
| Check for restrictions in air flow around unit and vent terminal. |
|
| Check for low water flow in a circulating system causing |
|
| Ensure dip switches are set to the proper position. |
|
| Check for foreign materials in combustion chamber and/or exhaust piping. |
|
| Check heat exchanger for cracks and/or separations. |
|
| Check heat exchanger surface for hot spots which indicate blockage due to |
|
| scale buildup. |
|
| Refer to instructions in manual for flushing heat exchanger. |
|
| Measure resistance of safety circuit. |
|
| Ensure high fire and low fire manifold pressure is correct. |
|
| Check for improper conversion of product. |
16 | Over Temperature Warning | Check for restrictions in air flow around unit and vent terminal. |
|
| Check for low water flow in a circulating system causing |
|
| Check for foreign materials in combustion chamber and/or exhaust piping. |
|
| Check for clogged heat exchanger. |
32 | Outgoing Water Temperature Sensor | Check sensor wiring for damage. |
| Fault | Measure resistance of sensor. |
Clean sensor of scale
Replace sensor.
33Heat Exchanger Outgoing Temperature Check sensor wiring for damage.
| Sensor Fault |
| Measure resistance of sensor. | |
|
|
|
| Clean sensor of scale |
|
|
|
| Replace sensor. |
34 | Combustion | Air Temperature Sensor | Check for restrictions in air flow around unit and vent terminal. | |
| Fault |
|
| Check sensor wiring for damage. |
|
|
|
| Measure resistance of sensor. |
|
|
|
| Clean sensor of scale |
|
|
|
| Ensure fan blade is tight on motor shaft and is in good condition. |
|
|
|
| Replace sensor. |
52 | Modulating | Solenoid | Valve Signal | Check modulating gas solenoid valve wiring harness for loose or damaged |
| Abnormal |
|
| terminals. |
|
|
|
| Measure resistance of valve coil. |
61 | Combustion | Fan Failure | Ensure fan will turn freely. | |
|
|
|
| Check wiring harness to motor for damaged and/or loose connections. |
|
|
|
| Measure resistance of motor winding. |
65 | Water Flow Control | Fault | If blank screen is present on remote control then the flow control has | |
|
|
|
| shorted. Unplug flow control. If remote lights up and unit starts operating |
|
|
|
| then replace flow control assembly. |
71SV0, SVl, SV2, and SV3 Solenoid Valve Check wiring harness to all solenoids for damage and/or loose connections.
| Circuit | Fault |
|
|
| Measure resistance of each | solenoid valve coil. |
| |
72 | Flame | Sensing Device | Fault |
| Ensure flame rod is touching | flame when unit fires. |
| ||
|
|
|
|
|
|
| Check all wiring to flame rod for damage. |
| |
|
|
|
|
|
|
| Remove flame rod and check for carbon | ||
|
|
|
|
|
|
| Check inside burner chamber for any foreign material blocking flame at | ||
|
|
|
|
|
|
| flame rod. |
|
|
|
|
|
|
|
|
| Measure micro amp output of sensor circuit with flame present. | ||
|
|
|
|
|
|
| Replace flame rod. |
|
|
LC or | Scale | Exchanger | (when | Flush heat exchanger. See Flushing the Heat Exchanger | section. | ||||
O0 | checking | maintenance | code history, "00" |
|
|
| |||
| is substituted for | "LC") |
|
|
|
|
| ||
No | Nothing | happens | when water | flow is | Clean inlet water supply filter. |
| |||
Code | activated. |
|
|
|
| On new installations ensure | hot and cold water lines are | not reversed. | |
|
|
|
|
|
|
| Check for bleed over. |
|
|
Isolate unit from building by turning off hot water line to building. Isolate the circulating system if present. Open your pressure relief valve; if water is flowing, there is bleed over in your plumbing.
Ensure you have at least the minimum flow rate required to fire unit. Ensure turbine spins freely.
Measure the resistance of the water flow control sensor.
Check for DC shorts at components.