Installation
With 18 alarms interconnected, it is still possible to interconnect up to a total of 6 remote signaling devices and/or relay modules.
•The maximum wire run distance between the first and last unit in an interconnected system is 1000’ (305 m).
•Make certain alarms are wired to a continuous, (non- switched) power line. NOTE: Use standard UL Listed household wire (18 gauge or larger as required by local codes) available at all electrical supply stores and most hardware stores.
Wiring
Figure 1 illustrates interconnection wiring. Improper connection will result in damage to the alarm, failure to operate, or a shock hazard.
CAUTION! Turn off the main power to the circuit before wiring the alarm.
FIGURE 1 INTERCONNECT WIRING
4
Wires on the A.C.
Black | Connected to hot side of A.C. line. |
White | Connected to neutral side of A.C. line. |
Red | Connected to interconnect lines (red wires) |
| of other units in a |
8