Kidde P/N 900-0120, KN-COB-IC specifications Wiring, Installation

Models: KN-COB-IC P/N 900-0120

1 25
Download 25 pages 5.29 Kb
Page 8
Image 8
Wiring

Installation

With 18 alarms interconnected, it is still possible to interconnect up to a total of 6 remote signaling devices and/or relay modules.

The maximum wire run distance between the first and last unit in an interconnected system is 1000’ (305 m).

Make certain alarms are wired to a continuous, (non- switched) power line. NOTE: Use standard UL Listed household wire (18 gauge or larger as required by local codes) available at all electrical supply stores and most hardware stores.

Wiring

Figure 1 illustrates interconnection wiring. Improper connection will result in damage to the alarm, failure to operate, or a shock hazard.

CAUTION! Turn off the main power to the circuit before wiring the alarm.

FIGURE 1 INTERCONNECT WIRING

4

Wires on the A.C. Quick-Connector Alarm Harness:

Black

Connected to hot side of A.C. line.

White

Connected to neutral side of A.C. line.

Red

Connected to interconnect lines (red wires)

 

of other units in a multiple-station set-up.

8

Page 8
Image 8
Kidde P/N 900-0120, KN-COB-IC specifications Wiring, Installation