Kirby Air Control System Pre-Divecheck, TABLE Suggested Regulator settings for the KMACS, Metric

Models: 5 Air Control System

1 31
Download 31 pages 58.17 Kb
Page 16
Image 16
2.5 PRE-DIVE CHECK

KMACS 5 MANUAL

hoses to the mask or helmet, (refer to the manual for the mask or helmet for the proper connection procedures for your life support equipment). This action will prevent any foreign matter from entering the helmet or mask breathing system. Once the hose is blown out, immediately connect the fitting on the hose to the fitting on the mask or helmet.

Connect the communications portion of the diver’s umbilical to the communications fittings on the communicator and to the mask or helmet. Be sure the proper connection is made with the right com- munications line for each diver. The wires in the diver’s umbilical should be marked so it is easy to identify which plug connects to the earphone ter- minals and which plug connects to the microphone terminals.

2.5 PRE-DIVE CHECK

Prior to EVERY dive, the following should be checked:

With the free flow and demand regulator on the mask/helmet(s) shut off, turn on the air supply at each of the air cylinders. During operation with scuba bottles as the main supply, the selector valve handle must be FULLY up or FULLY down. Fully up turns the “BLUE” supply on and the “ORANGE” supply off. Fully down turns the “ORANGE” sup- ply on and the “BLUE” supply off.

Note the air pressure in each cylinder by reading the gauges (L,M). The low pressure supply should be switched “OFF” at the source at this time. A check valve in the low pressure system prevents back flow to the compressor.

Both cylinders should be full prior to diving. Load the regulator on the KMACS 5 using the regulator adjustment knob (H). Observe the umbilical hose pressure (B) which should be set at 150 psi (10.3 bars) over top side pressure, or 165 psi (11.5 bars) The regulator used in the KMACS 5 is a non-vent- ing regulator. If the regulator has been left set at a higher pressure setting than is presently desired, the operator must turn the regulator adjustment knob (H) clockwise and vent air from the system

by bleeding either the pneumo system or diver’s breathing apparatus.

As the diver descends, the KMACS 5 operator should increase the regulator setting so that the

umbilical pressure is always 150 psi (10.3 bars) over the pressure at the diver’s depth. Consult the table below for approximate pressure settings.

TABLE 1

Suggested Regulator settings for the KMACS 5

 

Depth - fsw

Pressure

Optimal

Minimum

 

0’

14.7 psia

150 psig

150 psig

 

 

 

 

 

 

33’

29.4 psia

165 psig

150 psig

 

66’

44.1 psia

180 psig

150 psig

 

99’

58.8 psia

195 psig

160 psig

 

132’

73.5 psia

210 psig

175 psig

 

165’

88.2 psia

225 psig

190 psig

 

198’

102.9 psia

225 psig

205 psig

 

 

 

 

 

TABLE 1, Metric

Suggested Regulator settings for the KMACS 5

 

 

 

Depth-Meters

Pressure

Optimal

Minimum

0

1 bar

10.3 bars

10.3 bars

 

 

 

 

 

 

 

 

10

2 bars

11.4 bars

10.3 bars

20

3 bars

12.4 bars

10.3 bars

 

 

 

30

4 bars

13.4 bars

11.0 bars

40

5 bars

14.5 bars

12.1 bars

 

 

50

6 bars

15.5 bars

13.1 bars

60

7 bars

15.5 bars

14.1 bars

2.5.1 TESTING L.P. SUPPLY

With the air on at the bottles and the communications switched on, check the regulator function. The diver should insert his face in the mask/helmet and take several breaths to test the demand regulator.

To test the low pressure supply, place the selector valve handle (I) in the “H.P. OFF” zone and the console will be running off the low pressure supply only. Observe the umbilical pressure gauge (B). As the compressor cycles, the gauge will rise and fall as the compressor’s volume tank fills and empties. The maximum pressure for the L.P. inlet should be 225 psi. Again, check the mask/helmet function which will also confirm the low pressure supply routing.

10

© 2003 KMDSI Document # 041112001

 

Page 16
Image 16
Kirby Air Control System, 5 Pre-Divecheck, TABLE Suggested Regulator settings for the KMACS, Metric, Testing L.P. Supply