The chimneys can be adjusted for different ceiling heights. See the following chart.

Vented Installations

 

Min. ceiling height

Max. ceiling height

 

 

 

Electric cooking

7' 9" (2.36 m)

9' 10" (3.0 m)

surface

 

 

Gas cooking

8' (2.44 m)

9' 10" (3.0 m)

surface

 

 

 

Non-Vented (Recirculating) Installations

 

 

 

 

Min. ceiling height

Max. ceiling height

 

 

 

Electric cooking

7' 9" (2.36 m)

10' 4" (3.15 m)

surface

 

 

Gas cooking

8' (2.44 m)

10' 4" (3.15 m)

surface

 

 

Venting Methods

This island hood is factory set for venting through the roof.

A 6" (15.2 cm) round vent system is needed for installation (not included). The hood exhaust opening is 6" (15.2 cm) round.

NOTE: Flexible vent is not recommended. Flexible vent creates back pressure and air turbulence that greatly reduce performance.

Vent system can terminate either through the roof or wall. To vent through a wall, a 90° elbow is needed.

For Non-Vented (recirculating) Installations

If it is not possible to vent cooking fumes and vapors to the outside, the hood can be used in the non-vented (recirculating) version, using a Recirculation Kit (which includes charcoal filters and a deflector). To order, see the “Assistance or Service” section.

*NOTE: The range hood chimneys are adjustable and designed to meet varying ceiling or soffit heights depending on the distance “C” between the bottom of the range hood and the cooking surface. For higher ceilings, a Stainless Steel Chimney Extension Kit Part Number W10272078 is available from your dealer or an authorized parts distributor. The chimney extension replaces the upper chimney shipped with the range hood.

Venting Requirements

Vent system must terminate to the outside, except for non-

vented (recirculating) installations.

Do not terminate the vent system in an attic or other enclosed

area.

Do not use 4" (10.2 cm) laundry-type wall caps.

Use metal vent only. Rigid metal vent is recommended. Do

not use plastic or metal foil vent.

The vent system must have a damper. If the roof or wall cap

Roof Venting

A

B

Non-Vented (Recirculating)

A

B

has a damper, do not use the damper supplied with the range

hood.

For the Most Efficient and Quiet Operation:

Use a straight run or as few elbows as possible.

Use no more than three 90° elbows.

Make sure there is a minimum of 24" (61.0 cm) of straight vent between the elbows if more than 1 elbow is used.

Do not install 2 elbows together.

Use vent clamps to seal all joints in the vent system.

Use caulking to seal exterior wall or roof opening around the cap.

The size of the vent should be uniform.

Cold Weather Installations

An additional back draft damper should be installed to minimize backward cold air flow and a thermal break should be installed to minimize conduction of outside temperatures as part of the vent system. The damper should be on the cold air side of the thermal break.

The break should be as close as possible to where the vent system enters the heated portion of the house.

Makeup Air

Local building codes may require the use of makeup air systems when using ventilation systems greater than specified CFM of air movement. The specified CFM varies from locale to locale.

Consult your HVAC professional for specific requirements in your area.

A. Roof cap

A. Deflector

B. 6" (15.2 cm) round vent

B. 6" (15.2 cm) round vent

NOTE: Wall venting can be an option for 2-story homes.

Calculating Vent System Length

To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system.

Vent Piece

6" (15.2 cm) Round

45° elbow

2.5 ft

 

(0.8 m)

90° elbow

5.0 ft

 

(1.5 m)

Maximum equivalent vent length is 35 ft (10.7 m).