Electrical connection

Electrical connection

The built-in cooking area must be connected to the mains supply by a qualified electrician who is authorized to carry out such work.

Both legal wiring regulations and the requirements of your local electricity supply board must be fully complied with.

When connecting the hob, a device must be provided which enables all- pole disconnection of the hob from the supply with a gap construction of at least 3 mm. Circuit breakers, fuses and contactors are considered to be suitable disconnecting units.

When connecting and repairing the appliance disconnect it from the elec- tricity supply with one of these devices.

Overall protection against electric shock must be ensured by the installation.

The earthed conductor lead must be sufficiently long so that, in the event of failure of the strain relief, it is not subjected to strain until after the live wires of the connection cable.

Any superfluous cable must be removed from the installation area beneath the appliance.

At the factory the electronic hob has been equipped with a temperature-proof cable with a connecting box for the oven connection cable.

The connecting box is fastened to the kitchen wall behind the built-in furniture. If there is no built-in oven below the hob, the connecting box can also be fa- stened to the furniture below the hob.

When assembling the connecting box remember that it must be at least 300 mm from the floor, as shown in the drawing.

The connecting box must not come into contact with any hot appliance parts.

The connecting box must not be used as a voltage distributor for other appliances.

The appliance is connected to the mains at the connecting box as shown in the wiring diagram. The connection may only be made in the connector box.

The connector box must not be removed.

The fitted connection cable must be replaced by the KÜPPERSBUSCH Cu- stomer Service if it becomes damaged.

The green-yellow earth conductor must be longer than the other wires.

Connection diagram:

Electrical

Permanent connection by means of an oven connection

connection

socket.

 

Connection

is depicted on the underside of the appliance, suitable for

diagram

the various types of mains.

Connection data

Permanent connection 400 V 3 N ~ 50 Hz

 

(AC 230 V in UK)

 

Voltage of heating element: 230 V

 

Total connection output: 10.4 kW

 

400

V 3 N ~ safety current 16 A

 

400

V 2

N ~ safety current 20 A

 

230

V 1

N ~ safety current 25 A

 

230

V 3

~ safety current 16 A

Connection cable

Use H 05 RR-F or H 07 RN-F. Length of cable as necessary.

[When assembling the connecting box remember that it must be at least 300 mm from the floor, as shown in the drawing.

Single-phase connection 230 V phase against neutral conductor

Cable to the hob

Supply line from cooker junktion box

The conductor colours may be different. The connection diagram and the terminal numbers are the decisive factors.

base

Three-phase connection 400 V system with 230 V phase against neu- tral conductor

Three-phase system 230 V phase against phase

[Caution: Incorrect connection results in the total destruction of the power electronics.