3: Operations
2. On the subsequent Serial Port Edit page, enter the descriptive name. Up to 24
alphanumeric and other typeable characters (ASCII 33 to 126 decimal, spaces
and colon characters are not allowed) are allowed. Press Apply.
Note: Port names ‘1’ thru ‘64’ and ‘CONSOLE’ are reserved system names
and may not be used.
Enabling or disabling serial port active signal checking:
1. Click on the Edit link in the Action column next to the port to be configured.
2. On the subsequent Serial Port Edit page, select On or Off from the DSR Check
drop-down menu and press Apply.
Outlets
The Outlets configuration page is used for assignment and/or editing of outlet
descriptive names and wakeup states.
Setting the outlet sequencing interval:
1. Enter the sequencing interval (in seconds) in the Sequencing Interval field and
press Apply.
Setting the outlet reboot delay:
2. Enter the reboot interval (in seconds) in the Reboot Delay field and press Apply.
Editing the outlet descriptive name:
1. Click on the Edit link in the Action column next to the outlet to be configured.
2. On the subsequent Outlet Edit page, enter the descriptive name. Up to 24
alphanumeric and other typeable characters (ASCII 33 to 126 decimal, spaces
and colon characters are not allowed) are allowed. Press Apply.
Changing the outlet wakeup state:
1. Click on the Edit link in the Action column next to the outlet to be configured.
2. On the subsequent Outlet Edit page, select On, Off, or Last from the Wakeup
State drop-down menu and press Apply.
Setting the outlet Post-On delay:
3. Click on the Edit link in the Action column next to the outlet to be configured.
4. On the subsequent Outlet Edit page, enter the outlet Post-On delay (in seconds)
in the Post-On Delay field and press Apply.
Groups
The Groups configuration page is used for creation and deletion of group and
assignment of outlets to groups.
Creating a group:
SecureLinx SLP Remote Power Manager 22