3: Operations
Example
The following command adds the descriptive name DataServer_1 to outlet .a1:
SLP: set outlet name .a1 DataServer_1<Enter>
Setting the outlet wakeup state
The Set Outlet Wakeup command set the default wakeup state for that outlet. In the
event of a system-wide power loss, this state will be applied to the outlet when power
is restored.
The wakeup state may be set to On, Off, or Last. Upon restoration of system power;
If set to On, the unit will apply power to that outlet. If set to Off, the unit will not apply
power to that outlet.
To set the wakeup state:
1. At the command prompt, type set outlet wakeup, followed by on or off and
the outlet name. Press Enter.
Example
The following command sets the wakeup state for outlet .a1 to off:
SLP: set outlet wakeup off .a1<Enter>
Displaying outlet information
The Show Outlets command displays information about all outlets. This information
includes:
Descriptive outlet name, if applicable
Outlet wakeup state setting
To display outlet information:
1. At the command prompt, type show outlets and press Enter.
Example
The following command displays all outlet information:
SLP: show outlets<Enter>
Outlet Outlet Wakeup
ID Name State
.A1 DataServer_1 off
.A2 WebServer_1 on
.A3 FileServer_1 on
.A4 on
.A5 on
.A6 on
.A7 on
.A8 on
.A9 on
.A10 on
.A11 on
.A12 on
.A13 on
.A14 on
.A15 on
SecureLinx SLP Remote Power Manager 50