INSTALLATION
MODEL L20 BF-2 ONLY
This appliance is designed to be vented with a 4”
B-Vent Installation Illustration
Approved for vertical termination only.
| Vertical |
| Termination |
Firestops must be | Only |
used when vent |
|
pipe passes |
|
through a floor or |
|
ceiling |
|
Horizontal runs | 25 | |
Feet | ||
require ¼” rise | ||
Max. | ||
per foot. | ||
|
See chart
5 Feetbelow to
Min.determine horizontal run allowed
Model L20 BF-2
Maximum Horizontal Pipe Runs
for Given Vertical Pipe Run (in feet)
Vertical run | 5’ | 6’ | 8’ | 10’ | 15’ | 20’ | |
in feet | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
Maximum horizon- | 4’ | 6’ | 8’ | 10’ | 15’ | 20’ | |
tal run in feet | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
|
Note: Maximum allowable horizontal pipe run is 20 feet.
Vent Configuration Requirements
A minimum of 5 feet vertical pipe is required to vent the ap- pliance. Lengthy horizontal pipe runs require sufficient length of vertical pipe to deliver adequate draft. Use the table above as a guide in planning your installation. The use of multiple 45° or 90° elbows should be compensated by providing addi- tional vertical pipe run.
The
Notes:
Maximum total offsets allowed: Not to exceed 180 de- grees.
Also see pipe manufacturers instructions for additional vent installation requirements.
Horizontal vent clearances: 3“ minimum top, 1“ mini- mum on bottom and sidewalls.
Vertical vent clearances: 1” minimum.
Install vent support brackets every 4 feet of vertical pipe unless otherwise specified by vent manufacturer.
For vent termination requirements, see page 10
PAGE 11