Usesheetmetalshearstoremovethecutoutfromtheside ofthecabinetUsethetwoprovidedsheetmetalscrewsto. installthecutoutonthetopcaptocovertheoriginalflue
outletopeningSeefigure15. .
thelatesteditionof NationalFuelGasCode(NFPA54/
ANSI Z223.1 ) in the USA and the current standards of CSA B149 Natural Gas and Propane Installation Codes in Can- ada. A
NOTE - Use these instructions as a guide. They do not su- persede local codes. This furnace must be vented accord- ing to all local codes these installation instructions, and the provided venting tables in these instructions
The venting tables in this manual were extracted from the National Fuel Gas Code (NFPA 54 / ANSI Z223.1 ) and are provided as a guide for proper vent installation. Proper ap- plication, termination, construction and location of vents must conform to local codes having jurisdiction. In the ab- sence d local codes, the NFGC serves as the defining doc- ument.
Refer to the tables and the venting information contained in these instructions to properly size and install the venting system.
klMPORTANT
kWARNING
VENT CONNECTION
VENT
PIPE
FURNACE
FLUE TRANSITIOF
COLLAR
FIGURE 16
Use
flue transition. If
Install the first vent connector elbow at a minimum of six inches (152 mm) from the furnace vent outlet.
Venting Using a Masonry Chimney
The following additional requirements apply when a lined masonry chimney is used to vent this furnace.
Masonry chimneys used to vent Category I central fur- naces must be either
lining system or dedicated gas vent. Unlined masonry chimneys are prohibited. See figures 17 and 18 for com- mon venting.
A chimney with one or more sides exposed to the outside of the structure is considered to be an exterior chimney.
An exterior masonry chimney that is not
An exterior tileqined chimney that is sealed and capped may be lined with a listed uninsulated flexible metal vent.
If the existing chimney will not accommodate a B1 vent or
an insulated flexible vent pipe liner, either the chimney must be rebuilt to accommodate one of these liners or an
alternate approved venting method must be found. Insulation for the flexible vent pipe must be an encapsu- lated fiberglass sleeve recommended by the flexible vent pipe manufacturer. See figure 17.
G50UH units installed in upflow applications may be vented into a
DO NOT insulate the space between the liner and the chimney wall with puffed mica or any other loose gran- ular insulating material
Common Venting Using
|
|
| SEALED |
|
|
| / |
T | MAX. LENGTH |
|
|
|
|
| |
| BELOW. | II |
|
|
|
| |
|
| II | CHIMNEYEXTERIORWITH |
|
| II | METAL |
VE%OO.o%OTOR " | II | LINER | |
'1 |
| ||
|
|
|
__ .,J
PERMANENTLY
SEALED FIREPLACE
OPENING
NOTE 1 - Refer to the provided venting tables for installations in the USA and the venting tables in CSA B149 for installations Canada.
NOTE 2 - Either
FIGURE 17
Page 13