TABLE 3

Capacity of Type B Double-WallVents with Type B Double-Wall Connectors

Serving a Single Category I Appliance

 

 

 

 

Vent and Connector Diameter - D (inches)

 

 

Height

Lateral

 

3 Inch

 

4 Inch

 

5 Inch

 

6 Inch

H

L

 

 

 

 

 

 

 

 

(feet)

(feet)

 

 

Appliance

Input Rating

in Thousands

of Btu Per Hour

 

 

 

 

MIN

MAX

MIN

MAX

MIN

MAX

MIN

MAX

 

0

0

78

0

152

0

251

0

375

 

2

13

51

18

97

27

157

32

232

6

4

21

49

30

94

39

153

50

227

 

 

6

25

46

36

91

47

149

59

223

 

0

0

84

0

165

0

276

0

415

8

2

12

57

16

109

25

178

28

263

5

23

53

32

103

42

171

53

255

 

 

8

28

49

39

98

51

164

64

247

 

0

0

88

0

175

0

295

0

447

 

2

12

61

17

118

23

194

26

289

10

5

23

57

32

113

41

187

52

280

 

 

10

30

51

41

104

54

176

67

267

 

0

0

94

0

191

0

327

0

502

 

2

11

69

15

136

20

226

22

339

15

5

22

65

30

130

39

219

49

330

 

10

29

59

40

121

51

206

64

315

 

15

35

53

48

112

61

195

76

301

 

0

0

97

0

202

0

349

0

540

 

2

10

75

14

149

18

250

20

377

 

5

21

71

29

143

38

242

47

367

20

10

28

64

38

133

50

229

62

351

 

 

15

34

58

46

124

59

217

73

337

 

20

48

52

55

116

69

206

84

322

 

0

0

100

0

213

0

374

0

587

 

2

9

81

13

166

14

283

18

432

 

5

21

77

28

160

36

275

45

421

30

10

27

70

37

150

48

262

59

405

 

15

33

64

44

141

57

249

70

389

 

20

56

58

53

132

66

237

80

374

 

30

NR

NR

73

113

88

214

104

346

NOTE - Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other

vent configurations, the vent system is assumed to have two 90 ° elbows. For each additional 90 ° elbow or equivalent (for example two 45 ° elbows equal one 90 ° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi-

mum listed capacity).